The following explains a typical procedure to be followed
in checking gas pressures.
Consult the dataplate on the heater or page 4 in this
manual for specific pressures to be used in conjunction
with this procedure. The gas pressures will vary
depending upon fuel type.
Gas pressure measured at the inlet to the gas valve is
Inlet Pressure and gas pressure measured at the outlet
of the gas valve is Burner Manifold Pressure.
MATERIALS REQUIRED
(To be secured through local purchase)
Quantity
Description
2
Gas pressure gauges capable of reading
up to 8.7 kPa. (may also be ordered
from L.B. White, part number 00764)
A. Preparation
1. Disconnect the heater from the electrical supply and
close the fuel supply valve to the heater inlet.
2. Open the case access panel at gas inlet end of
heater.
3. Brush or blow off any dust or dirt in the vicinity of the
gas control valve.
B. Gauge Installation
1. Locate the inlet and outlet pressure taps, see Fig. 16.
Remove the pressure tap plugs using a 3/16 in. allen
key.
2. Securely connect pressure gauges.
3. Open the fuel supply valves to the heater, reconnect
the heater electrical supply, and start the heater.
FIG. 16
OUTLET
GAUGE
OFF
ON
OUTLET TAP
GAS CONTROL
LOW HEAT
TYPICAL PRESSURE GAUGE INSTALLATION. ALWAYS
REFER TO DATA PLATE FOR FUEL TYPE AND
PRESSURE REQUIREMENTS.
INLET
GAUGE
LO
HI
INLET TAP
HIGH HEAT

Gas Pressure Checks

C. Reading Pressures
1. With the heater operating, the pressure gauges
should read the pressures specified on the dataplate.
2. Do the readings at the inlet and outlet pressure
gauges agree with that specified on the dataplate?
If so, then no further checking or adjustment is
required. Proceed to section D.
3. If the inlet pressures do not agree with that specified
on the dataplate, then the regulator controlling gas
pressure to the heater requires adjustment.
4. If the inlet pressure is correct but the burner manifold
pressure does not agree with that specified on the
dataplate, then the HI and LO heat output feature of
the gas control valve requires adjustment.
5. Turn the thermostat down to its lowest setting.
Remove the cap from the HI and LO heat adjusting
screws at the two stage pressure regulator on the gas
control valve.
6. Slowly turn up the thermostat until the valve opens in
first stage position and a pressure is read of no
greater than .35 kPa. (L.P.) or .2 kPa. (N.G.) at the
outlet pressure gauge. If less than .35 kPa. (L.P.) or
.2 kPa. (N.G.) is read, the LO heat setting at the
regulator on the gas control will require adjusting.
Turn clockwise to increase, or counterclockwise to
decrease.
7. Turn the thermostat completely up. You should see
the valve open at second stage position and the gas
pressure increase from .35 kPa. (L.P.) or .2 kPa. (N.G.)
at first stage heat to 1.25 kPa. (L.P.) or 0.77 kPa.
(N.G.) second stage heat. If less or greater than
1.25.kPa. (L.P.) or 0.77 kPa. (N.G.), the HI heat setting
must be adjusted clockwise or counterclockwise
accordingly until proper pressure is achieved.
D. Completion
1. Once the proper inlet and burner manifold pressures
have been confirmed and/or properly set, close the
fuel supply valve to the heater and allow the heater to
burn off any gas remaining in the gas supply line.
2. Disconnect the heater from its electrical supply.
3. Remove the gauges.
4. Install pressure tap plugs.
5. Open fuel supply valve. Start the heater and check
for gas leaks.
6. Set thermostat to desired temperature.