Boiler Default Settings - Aerco Benchmark 2.0 Installation, Operation & Maintenance Instructions Manual

Low nox gas fired boiler system
Table of Contents

Advertisement

MENU & OPTION
Setup Menu
Password
Language
Unit of Temp
Comm Address
Baud Rate
Configuration Menu
Internal Setpt
Unit Type
Unit Size
Boiler Mode
Remote Signal
(If Mode = Remote Setpoint, Direct Drive or
Combination)
Bldg Ref Temp
(If Boiler Mode = Outdoor Reset)
Reset Ratio
(If Boiler Mode = Outdoor Reset)
Outdoor Sensor
System Start Tmp
(If Outdoor Sensor = Enabled)
Setpt Lo Limit
Setpt Hi Limit
Temp Hi Limit
Max Valve Position
Pump Delay Timer
Aux Start On Dly
Failsafe Mode
Analog Output
Lo Fire Timer
Setpt Limit Band (If Setpt Limiting = Enabled)

BOILER DEFAULT SETTINGS

FACTORY DEFAULT
0
English
Fahrenheit
0
9600
130°F
BMK Boiler LN
2.0 MBTU
Constant Setpoint
4 – 20 mA / 1-5V
70°F
1.2
Disabled
60°F
60°F
200°F
215°F
100%
0 min
0 sec
Shutdown
Valve Position 0-10V
CAUTION: DO NOT Change
2 sec
5°F
APPENDIX E
E-1