INSTALLATION MANUAL
CONDENSING UNITS
ASE-18AH, ASE-24AH, ASE-30AH
ASE-36AH, ASE-48AH, ASE-60AH

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ASE-36AH and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Sinclair ASE-36AH

  • Page 1 INSTALLATION MANUAL CONDENSING UNITS ASE-18AH, ASE-24AH, ASE-30AH ASE-36AH, ASE-48AH, ASE-60AH...
  • Page 3 Install according to this installation instructions strictly. PRECAUTIONS If installation is defective, it will cause water leakage, electrical shock and fire. When installing the unit in a small room, take measures against to keep refrigerant concentration from exceeding keep this manual where the operator can easily find them. allowable safety limits in the event of refrigerant leakage.
  • Page 4: Installation Information

    If the refrigerant leaks during installation, ventilate the An all-pole disconnection device which has at least 3mm area immediately. clearances in all poles , and have a leakage current that Toxic gas may be produced if the refrigerant comes into the may exceed 10mA, the residual current device (RCD) place contacting with fire.
  • Page 5: Outdoor Unit Installation

    6.2 Figure of body size OUTDOOR UNIT INSTALLATION Split type outdoor unit Installation Place The outdoor unit should be installed in the location that meets the following requiements: There is enough room for installation and maintenance. The air outlet and the air inlet are not impeded, and can not be reached by strong wind.
  • Page 6: Moving And Installation

    Table 6-1 unit:mm 6.5 Moving and installation MODEL REMARK Since the gravity center of the unit is not at its physical center, so please be careful when lifting it with a sling. Fig.6-2 Never hold the inlet of the outdoor unit to prevent it from Fig.6-2 deforming.
  • Page 7: Install The Connecting Pipe

    7. INSTALL THE CONNECTING PIPE Table 6-4 Description Check whether the height drop between the indoor unit and Outdoor Unit outdoor unit, the length of refrigerant pipe, and the number of the bends meet the following requirements: Vibration-proof rubber (The number of the bends less than 15) Anchor Bolt M10 Table 7-1 Drainage (Wide 100×Depth 150)
  • Page 8 Remove the protection cover of stop valve Bind the connecting pipe and the cables together tightly with binding tapes.Pass the bound connecting pipe through the wall conduct from outside. Be careful of the pipe allocation to do on damage to the tubing. Connect the pipes.
  • Page 9: Additional Refrigerant Charge

    Closing stop valve Manifold valve Remove the cap and turn the valve clockwise with the Multi-meter Pressure meter hexagon wrench. -76 cmHg Securely tighten the valve until the shaft contacts the Hi-lever Lo-lever main bodyseal. Charge hose Charge hose Make sure to tighten the cap securely. Vacuum pump For the tightening torque, refer to the table below.
  • Page 10: Drainage Test

    CAUTION The drain pipe of indoor unit must be heat insulated, or it will condense dew, as well as the connections of the indoor unit. Hard PVC binder must be used for pipe connection, and make sure there is no leakage. With the connection part to the indoor unit, please be noted not to impose pressure on the side of indoor unit pipes.
  • Page 11: The Specification Of Power

    NOTE NOTE All the figures in this manual are for explanation Remark per EMC Directive 2004/108/EC. purpose only. They may be slightly different from the air For to prevent flicker impressions during the start of the conditioner you purchased.The actual unit shall prevail. compressor (technical process)
  • Page 12 The Specification of Power(indoor power supply) Table 9-1 30~36 42~48 MODEL 1 P h a s e 1 P h a s e 1 P h a s e 1 P h a s e 1 P h a s e PHASE POWER FREQUENCY AND VOLT...
  • Page 13 The Specification of Power(independence power supply) Table 9-5 30~36 42~48 MODEL 1 P h a s e 1 P h a s e 1 P h a s e 1 P h a s e 1 P h a s e PHASE POWER (indoor)
  • Page 14: Wiring Figure

    CAUTION The power supply is included in the power supply above mentioned can be applied to the table. Wiring figure Fig.9-5 Power supply Switch/Fuse (Available locally) Power wiring (indoor) Power linking wiring (Outdoor) Indoor Outdoor Unit Unit Ground wiring Strong elec-signal link wiring Ground wiring Weak elec-signal link wiring Ground the air conditioner properly in case to affect its anti-interference function...
  • Page 15 Fig.9-7 Power supply Power supply Switch/Fuse (Available locally) Power wiring (indoor) Power linking wiring (Outdoor) Indoor Unit Out door Unit Ground wiring Weak elec-signal link wiring Ground wiring Ground the air conditioner properly in case to affect its anti-interference function CAUTION A disconnection device having an air gap contact separation in all active conductors should be incorporated in the fixed wiring according to the National Wiring Regulation.
  • Page 16 185/2001 Coll., in the wording of later regulations. In case of incorrect disposal of this waste, a fine can be imposed according to national regulations. Manufacturer: Sinclair Corporation Ltd., 1-4 Argyll Street, London W1F 7LD, UK Supplier and technical support: Nepa, spol.s.r.o.