• Turn the AC input breakers ON.
BYPASS
OUTPUT INPUT
If the FX's AC source is available, the yellow AC IN
STATUS light will blink. The FX will connect to the
utility grid when the voltage is within 108-140 VAC and
the frequency between 59.3-60.5 Hz. After about 30
seconds, the AC IN light should stop blinking and stay
lit. A five-minute waiting period begins before selling
or charging can occur. The FX can then perform a
battery charge using the available AC.
16