Configuration level

4.5.5 Continuous controller (inverse)

InP. 1 Ê
Out. 3 Â
ConF / Cntr:
ConF / Out. 3 :
PArA / Cntr:
PArA / SEtP:
g
For direct action of the continuous controller, the controller action must be
changed ( ConF / Cntr / C. A ct = 1 ).
g
To prevent control outputs Out. 1 and Out. 2 of the continuous controller from
switching simultaneously, the control function of outputs Out. 1 and Out. 2 must
be switched off ( ConF / Out. 1 and Out. 2 / Y. 1 and Y. 2 = 0 ).
Configuration examples
SP. L O
InL. 1
20 mA
0/4 mA
SP. F n = 0
C. F nc = 1
C. A ct = 0
O. t YP = 1 / 2
Out. 0 = -1999...9999 scaling analog output 0/4mA
Out. 1 = -1999...9999 scaling analog output 20mA
Pb1
= 1...9999
ti1
= 0,1...9999
td1
= 0,1...9999
t1
= 0,4...9999
SP. L O = -1999...9999 set-point limit low for Weff
SP. H i = -1999...9999 set-point limit high for Weff
SP
PB1
set-point controller
continuous controller (PID)
inverse action
(e.g. heating applications)
Out. 3 type ( 0/4 ... 20mA )
proportional band 1 (heating)
in units of phys. quantity (e.g. °C)
integral time 1 (heating) in sec.
derivative time 1 (heating) in sec.
min. cycle time 1 (heating)