4.4.4 Heating and cooling with constant period ( CyCl= 3 )

1 and t2 are met in the overall
output range . To prevent
unreasonably short pulses, parameter
tp is used for adjusting the shortest
pulse duration. With small correcting
values which require a pulse shorter
than the value adjusted in tp, this
pulse is suppressed. However, the
controller stores the pulse and
totalizes further pulses, until a pulse
of duration tp can be output.
Parameters to be adjusted:
( PArA/ Cntr)
8800 process controller
tp
t1 t2
50%
t1 t2
50%
t1 : Min. cycle time 1 (heating) [s]
t2 : min. cycle time 2 (cooling) [s]
tp:
min. pulse length [s]
51
Configuration level
/
30%
20%
tp
/
70%
80%
Switching behaviuor
10%
90%