WEST 8800 Operating Manual page 36

Process controller
Table of Contents

Advertisement

Configuration level
Name
Value range Description
Src. 2
Fnc. 3
Configuration parameters
Source of limit 2
0
process value
1
control deviation xw (process value - set-point)
2
control deviation xw (with suppression after start-up and
set-point change)
After switch-on or set-point changing, the alarm output is
suppressed, until the process value is within the limits for the
first time. At the latest after elapse of time 10 ti1the alarm
is activated (ti1 = integral time 1; parameter r Cntr)
If ti1 is switched off (ti1 = 0), this is interpreted as Î ,
i.e. the alarm is not activated, before the process value was
within the limits once.
3
measured value INP1
4
measured value INP2
5
measured value INP3
6
effective setpoint Weff
7
correcting variable y (controller output)
8
control variable deviation xw (actual value - internal setpoint)
= deviation alarm to internal setpoint
9
difference x1 - x2 (utilizable e.g. in combination with process
value function "mean value" for recognizing aged
thermocouples
Function of limit 3
0
switched off
1
measured value monitoring
2
Measured value monitoring + alarm status storage. A stored
limit value can be reset via error list,
digital input ( -> LOGI/ Err. r )
3
signal change (change/minute)
4
signal change and storage (change/minute)
è
-key, Ò-key or a
36
8800 process controller
Default
0
0