Panasonic WH-MDC09C3E5 Servise Manual page 45

Monobloc air-to-water heatpump system
Hide thumbs Also See for WH-MDC09C3E5:
Table of Contents

Advertisement

• This equipment's power supply 2 shall be connected to a suitable supply network, with the following maximum permissible
system impedance Z
max
WH-MDC12C6E5, WH-MDC14C6E5, WH-MDC16C6E5 : 0.236Ω
Please liaise with supply authority to ensure that the power supply 2 is connected only to a supply of that impedance or less.
• The equipment's power supply 3 complies with IEC/EN 61000-3-12.
• This equipment's power supply 3 shall be connected to a suitable supply network, with the following maximum permissible
system impedance Z
max
WH-MDC12C6E5, WH-MDC14C6E5, WH-MDC16C6E5 : 0.464Ω
Please liaise with supply authority to ensure that the power supply 3 is connected only to a supply of that impedance or less.
11.4.3. Wired Remote Controller
1. Be sure to turn off the main power before installing and connecting the remote controller. Otherwise, it will cause the electrical shock.
2. Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, fire or electrical shock.
3. Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed properly, it will
cause fire or electrical shock.
4. Do not modify the length of the remote controller cable. Otherwise, it will cause fi re or electrical shock.
5. If passing the remote controller cable through a wall, be sure to install a water trap above the cable. Otherwise, it will cause the
electrical shock.
1. Install in a flat surface to avoid warping of remote controller, else damage to the LCD case or operation problems may result.
2. Avoid installing the remote controller cable near refrigerant pipes or water pipes, else will cause electrical shock or fire.
3. Install the remote controller cable at least 5cm away from electric wires of other appliances to avoid miss operation (electromagnetic
noise).
4. Be sure to use only the accessory screws to avoid damage of remote controller PCB.
Attached Accessories
No.
Name
(1)
Remote controller
(2)
Remote controller cable
(3)
Screw (M4 machine pitched - 30mm)
(4)
Screw (M4 self tapping - 14mm)
11.4.3.1. Selecting The Installation Location
• Allow sufficient space around the remote controller (1) as shown in the illustration above.
• Install in a place which is away from direct sunlight and high humidity.
• Install in a flat surface to avoid warping of the remote controller. If installed to a wall with an uneven surface, damage to the LCD
case or operation problems may result.
• Install in a place where the LCD can be easily seen for operation. (Standard height from the floor is 1.2 to 1.5 meters.)
at the interface of point for models:
at the interface of point for models:
Installation
Qty.
1
1
3
3
Diagram
Length (15 m)
Installing the remote controller to an outlet box
(embedded cable)
Installing the remote controller to the wall
(exposed cable)
45
Remark

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wh-mdc12c6e5Wh-mdc14c6e5Wh-mdc16c6e5

Table of Contents