Fujitsu ASYG30LMTA Design & Technical Manual page 36

Hide thumbs Also See for ASYG30LMTA:
Table of Contents

Advertisement

 When function setting is "Forced stop" mode
• In the case of "Edge" input
Rotary SW on
Function
External input and
setting /
output PCB
46-02
60-00 / 1
CN313
Indoor unit
Remote controller
• In the case of "Pulse" input
Rotary SW on
Function
External input and
setting /
output PCB
46-02
60-00 / 1
On
CN313
Off
On
CN314
Off
Forced stop
Normal
Operation
Indoorunit
Stop
Remote controller
NOTES:
• When the forced stop is triggered, indoor unit stops and Operation/Stop operation by the remote
controller is restricted.
• When forced stop function is used with forming a remote controller group, connect the same
equipment to each indoor unit within the group.
• This function is invalid when function setting 96 is set to "02" (Secondary unit).
-
Input of indoor unit
External input and
output PCB
On
Off
Forced stop
Normal
Operation
Stop
External input and
output PCB
- 32 -
External input
CN2
CN313
On
On
External input
CN313
CN314
On
On
Input signal
Command
Off → On
Forced stop
On → Off
Normal
Off → On
Forced stop
On → Off
Normal
On
Input signal
Command
Pulse
Forced stop
Pulse
Normal
On

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aoyg30lmtaAoyg36lmtaAsyg36lmta

Table of Contents