11) Switching functions for external output terminal
Functions of the external output terminal can be switched. For details, refer to "External input and
output".
Function number
60
12) Server room control
Switches between normal control and server room control.
NOTE: To use this function, address setting of the primary unit and secondary unit needs to be
done.
Function number
96
When performing server room control, mind the followings:
• Set to "01" on one of the 2 indoor units, and set to "02" on the other indoor unit.
• As for the function details and setup procedure, refer to
Setting value
00
09
10
Indoor unit fan operation status
12
Setting value
00
01
Server room control (Primary unit)
02
Server room control (Secondary unit)
- 44 -
Setting description
Operation status
Error status
Set point attainment status
Setting description
Normal control
"Details of server room control"
Factory setting
♦
Factory setting
♦
on page 4.