Rheem 610340 Owner's Manual And Installation Instructions page 14

Commercial storage tank
Hide thumbs Also See for 610340:
Table of Contents

Advertisement

INSTALLATION
Note: The storage tank should not be placed in direct contact with a concrete surface that is less than two
months old and not fully cured as this may attack the metal coating of the storage tank base. A moisture
barrier should be used between the two surfaces in this instance.
Remember all local authorities have regulations about putting storage tanks into roof spaces.
For a single storage tank installation, follow the
follow the
instructions on pages
SAFE TRAY
Where damage to property can occur in the event of the storage tank
leaking, the storage tank must be installed in a safe tray. Construction,
installation
and
draining
AS/NZS 3500.4
and
requirements. AS/NZS 3500.4 also has particular requirements when a
safe tray must be installed.
MAINS WATER SUPPLY
Where the mains water supply pressure exceeds that shown in the table below, an approved pressure
limiting valve is required and should be fitted as shown in the installation diagram
on page
20).
Model
Relief valve setting
Expansion control valve setting*
Max. mains supply pressure
With expansion control valve
Without expansion control valve
* Expansion control valve not supplied with storage tank
TANK WATER SUPPLY
If the storage tank is supplied with water from a tank supply and a pressure pump system is not installed,
then the bottom of the supply tank must be at least 1 m above the highest point of the hot water plumbing
system, including the storage tank. Care must be taken to avoid air locks. The cold water line to the storage
tank should be adequately sized and fitted with a full flow gate valve or ball valve. Consideration must be
given to any minimum water supply pressure requirements of water heater(s) which are part of the hot water
plumbing system.
24
to
29.
of
a
safe
tray must
all
local
codes
and
diagram on page
19. For multiple storage tank installations
comply with
regulatory authority
340, 430
1000kPa
850kPa
680kPa
800kPa
14
(refer to installation diagram

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

610430

Table of Contents