Address Setting - Mitsubishi Electric PURY-(E)P-YLM-A (-BS) Installation Manual

Air-conditioners for building application
Table of Contents

Advertisement

Available languages

Available languages

10-6. Address setting

・Set the address setting switch as follows.
Indoor unit (Main, Sub)
Outdoor unit (OC, OS)
Main
BC controller
HBC controller
Sub-HBC
Sub
Main
ME remote controller
Sub
MA remote controller
* The outdoor units in the same refrigerant circuit are automatically designated as OC and OS. The outdoor units are designated as OC and OS
in the order of capacity from large to small (if two or more units have the same capacity, in the order of address from small to large).
* Make indoor unit group settings from remote controllers after turning on the power to all units.
WT07282X01
Assign the lowest address to the main indoor unit in the group, and assign sequential
addresses to the rest of the indoor units in the same group.
* In an R2 system with a sub BC controller or in a Hybrid City Multi system with a
Sub-HBC, make the settings for the indoor units in the following order. (Set the
addresses so that the addresses of ① are smaller than those of ②, and the addresses
of ② are smaller than those of ③.)
Indoor units that are connected to the main BC controller or main HBC
controller
Indoor units that are connected to sub BC controller 1 or Sub-HBC
Indoor units that are connected to sub BC controller 2 or Sub-HBC
Assign sequential addresses to the outdoor units in the same refrigerant system.
* To set the address to 100, the address setting switch must be set to 50.
Assign an address that equals the address of the outdoor unit plus 1. If the address that
is assigned to the main BC controller or the main HBC controller overlaps any of the
addresses that are assigned to the outdoor units or to the sub BC controller or the
Sub-HBC, use a different, unused address within the setting range.
* To set the address to 100, the address setting switch must be set to 50.
Assign an address that equals the lowest address of the indoor units that are connected
to the sub BC controller or the Sub-HBC plus 50.
* To set the address to 100, the address setting switch must be set to 50.
Assign an address that equals the address of the main indoor unit in the group plus 100.
Assign an address that equals the address of the main indoor unit in the group plus 150.
Address setting is not required. (The Main/Sub setting is required.)
GB-52
Address setting method
Address
01 to 50
51 to 100
51 to 100
51 to 100
101 to 150
151 to 200

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents