Mitsubishi Electric PURY-(E)P-YLM-A (-BS) Installation Manual page 18

Air-conditioners for building application
Table of Contents

Advertisement

Available languages

Available languages

(3) Combination of face-to-face and side-by-side installations
When there are walls in the front and rear of the
block of units
h2'
500 (19-11/16)
Required minimum distance [mm (in)]
L2 (Right)
300 (11-13/16) + h2
300 (11-13/16) + h2'
Leave open in two directions.
WT07282X01
h2
500
(19-11/16)
L2
L4
L2'
L2' (Left)
L4 (Between)
900 (35-7/16)
When there are two walls in an L-shape
L3
Required minimum distance [mm (in)]
L2 (Right)
L3 (Right/Left)
300 (11-13/16) + h2
1000 (39-3/8) + h3
GB-16
h3
Unit height
L4
L4 (Between)
900 (35-7/16)
h2
500
(19-11/16)
L2