• Code 5042
[D-00]
0 (Default)
1
2
Remote Controller Setting Range : Code 10✴✴
Main Menu & Code
Remote Controller
Setting Range Code
10✴✴
Space Cooling
• Target water outlet temperature : Upper limit(#1011, Default 25ºC, Range : 18 ~ 25ºC),
- With this default FSV settings, user can change the target water outlet temperature within the range of 5 ~ 25ºC for
cooling
• Target room temperature : Upper limit(#1021, Default 30ºC), Lower limit(#1022, Default 18ºC)
- With this default FSV settings, user can change the target room temperature within the range of 18 ~ 30ºC for cooling.
Space Heating
• Target water outlet temperature : Upper limit(#1031, Default 55ºC, Range : 37 ~ 55ºC),
- With this default FSV settings, user can change the target water outlet temperature within the range of 25 ~ 55ºC for
heating.
• Target room temperature : Upper limit(#1041, Default 30ºC), Lower limit(#1042, Default 16ºC)
- With this default FSV settings, user can change the target room temperature within the range of 16 ~ 30ºC for heating.
DHW Heating
• Target DHW tank temperature : Upper limit(#1051, Default 50ºC, Range : 50 ~ 70ºC),
- With this default FSV settings, user can change the target tank temperature within the range of 40 ~ 50ºC for DHW
heating.
• The FSV #3011 in the wired remote controller should be set to "1(Yes)" to use DHW function.
NOTE
Compressor
Permitted
Permitted
Forced off
Field Setting Value
Sub Menu Function
Water Out Temp for Cooling
Room Temp for Cooling
Water Out Temp for Heating
Room Temp for heating
DHW Tank Temp
Lower limit(#1012, Default 16ºC, Range : 5 ~ 18ºC)
Lower limit(#1032, Default 25ºC, Range : 15 ~ 37ºC)
Lower limit(#1052, Default 40ºC, Range : 30 ~ 40ºC)
ENGLISH-39
Back up heater
Forced off
Forced off
Forced off
Description
Sub Code
Default Min
Max
✴✴11
Min
✴✴12
Max
✴✴21
Min
✴✴22
Max
✴✴31
Min
✴✴32
Max
✴✴41
Min
✴✴42
Max
✴✴51
Min
✴✴52
Booster heater
Permitted
Forced off
Permitted
Max
Step
25
18
25
1
16
5
18
1
30
28
30
1
18
18
28
1
55
37
55
1
25
15
37
1
30
18
30
1
16
16
18
1
50
50
70
1
40
30
40
1
Unit
˚C
˚C
˚C
˚C
˚C
˚C
˚C
˚C
˚C
˚C