TRDV SERIES
Do not install vent terminals on prevailing wind wall side of structure.
Moisture and ice may form around terminal. Make sure the surface is in good
repair and protected from damage.
Only Slant/Fin models TRDV boilers can be installed on sealed or direct
vented systems. They must be ordered from the factory with an approved
Direct Vent System. Part numbers for the kits and accessories can be found at
the back of this manual.
305 mm (12") min. above
ground or normally
expected snow
accumulation level
NOTE: Vacuum Relief Valve (VRV) not shown. VRV must be located as shown
on page 8.
FIGURE 3: Typical installation
ADDITIONAL INSTALLATION CONSIDERATIONS (Figures 2 & 3)
1) Kit or system may vary based on specific needs of appliance.
2) Utilize the appliance adapter test port for combustion testing required by appliance manufacturers.
TERMINAL
OUTER WALL PLATE
EXHAUST
AIR INLET
INNER WALL PLATE
The vent terminal has a 0 mm (0") clearance to combustibles
The insulator to vent pipe has 25 mm (1") clearance to combustibles.
STRAP
914 mm (36") MAX
TERMINAL ADAPTER
AIR INTAKE CLAMP
AIR INTAKE CLAMP
BURNER AIR ADAPTER
BURNER
VENT (SLOPING DOWN OR UP)
MIN. 21mm/m (1/4"/foot) SLOPE
APPLIANCE ADAPTER
WITH TEST PORT
APPLIANCE
3