Pipe Sizing - Buderus Logano plus GB312 Applications Manual

Gas condensing boiler
Table of Contents

Advertisement

GB312 Applications Manual

6.6 Pipe Sizing

For piping details, see Section 6.1
6.6.1 Three Boiler recommended Near Boiler Piping Size
"C"
Pump
PK
Three
GB312 System (18°F Delta T) Recommended Near Boiler Piping Size
Models
GB312/90
Pipe A
2½"
Pipe B
2"
Pipe C
1½"
Header E
2½"
Three
GB312 System (36°F Delta T) Recommended Near Boiler Piping Size
Models
GB312/90
Pipe A
2"
Pipe B
1½"
Pipe C
1¼"
Header E
2"
See Sections 10.1 and 10.2, Tables 17 to 20 for Boiler pump
(PK) and LLHeader (Hydro-Seperator) selections.
Logano plus GB312 applications manual | 04.2008
"C"
"B"
Pump
PK
GB312/120
GB312/160
GB312/200
3"
4"
4"
2½"
3"
3"
2"
2½"
2½"
3"
4"
4"
GB312/120
GB312/160
GB312/200
2½"
2½"
3"
2"
2"
2½"
1½"
1½"
2"
2½"
2½"
3"
"A"
"B"
"A"
Pump
PK
Table 16
GB312/240
GB312/280
4"
4"
4"
4"
2½"
3"
4"
4"
Table 17
GB312/240
GB312/280
3"
4"
2½"
3"
2"
2½"
3"
4"
Technical specifi cations are subject to change without prior notice
| 29
System
Supply
System
Return
"E"

Advertisement

Table of Contents
loading