Gas condensing boiler
Table of Contents

Advertisement

3 0 |
6.6.2 Four Boiler recommended Near Boiler Piping Size
"D"
Pump
PK
Four
GB312 System (18°F Delta T) Recommended Near Boiler Piping Size
Models
GB312/90
Pipe A
3"
Pipe B
2½"
Pipe C
2"
Pipe D
1½"
Header E
3"
Four
GB312 System (36°F Delta T) Recommended Near Boiler Piping Size
Models
GB312/90
Pipe A
2½"
Pipe B
2"
Pipe C
2"
Pipe D
1½"
Header E
2½"
See Sections 10.1 and 10.2, Tables 17 to 20 for Boiler pump (PK) and LLHeader (Hydro-Seperator) selections.
Technical specifi cations are subject to change without prior notice
"D"
"C"
Pump
PK
GB312/120
GB312/160
4"
4"
3"
4"
2½"
3"
2"
2½"
4"
4"
GB312/120
GB312/160
3"
3""
2½"
2½"
2"
2½"
1½"
2"
3"
3"
"C"
"B"
Pump
PK
Table 18
GB312/200
GB312/240
GB312/280
4"
5"
6"
4"
4"
4"
3"
4"
4"
2½"
3"
3"
4"
5"
6"
Table 19
GB312/200
GB312/240
GB312/280
4"
4"
4"
3"
3"
4"
2½"
2½"
3"
2"
2"
2½"
4"
4"
4"
GB312 Applications Manual
"A"
"B"
"A"
"E"
Pump
PK
Logano plus GB312 applications manual | 04.2008
System
Supply
System
Return