Viessmann VITODENS 200-W Installation And Service Instructions Manual page 87

Wall mounted gas condensing boiler
Table of Contents

Advertisement

Fault codes
(cont.)
Displayed
Const.
fault code
C4
X
C5
X
Cd
X
CF
d6
X
d7
X
d8
X
dA
db
dC
dd
dE
dF
E0
Weather-
System characteris-
comp.
tics
X
Control mode
X
Control mode, max.
pump speed
X
Control mode
X
Control mode
X
Control mode
X
Control mode
X
Control mode
X
Control mode without
room influence
X
Control mode without
room influence
X
Control mode without
room influence
X
Control mode without
room influence
X
Control mode without
room influence
X
Control mode without
room influence
X
Control mode
Cause
Measures
Communication er-
Check OpenTherm exten-
ror, OpenTherm
sion
extension
Communication er-
Check pump KM-BUS
ror, variable speed
pump
Communication er-
Check connections,
ror, Vitocom 100
Vitocom 100 and coding
(KM BUS)
address "95" in group
"General"/1
Communication er-
Replace LON communi-
ror, LON communi-
cation module
cation module
Input DE1 reports
Remove fault at appliance
a fault at EA1 ex-
concerned
tension
Input DE2 reports
Remove fault at appliance
a fault at extension
concerned
EA1
Input DE3 reports
Remove fault at appliance
a fault at extension
concerned
EA1
Short circuit, room
Check room temperature
temperature sen-
sensor, heating circuit 1
sor, heating circuit
1 (without mixer)
Short circuit, room
Check room temperature
temperature sen-
sensor, heating circuit 2
sor, heating circuit
2 (with mixer)
Short circuit, room
Check room temperature
temperature sen-
sensor, heating circuit 3
sor, heating circuit
3 (with mixer)
Lead break, room
Check room temperature
temperature sen-
sensor, heating circuit 1
sor, heating circuit
and remote control set-
1 (without mixer)
tings (see page 114)
Lead break, room
Check room temperature
temperature sen-
sensor, heating circuit 2
sor, heating circuit
and remote control set-
2 (with mixer)
tings (see page 114)
Lead break, room
Check room temperature
temperature sen-
sensor, heating circuit 3
sor, heating circuit
and remote control set-
3 (with mixer)
tings (see page 114)
Fault, external LON
Check connections and
subscriber
LON subscribers
Troubleshooting