Viessmann VITODENS 200-W Installation And Service Instructions Manual page 74

Wall mounted gas condensing boiler
Table of Contents

Advertisement

Code 2
Heating circuit 1, heating circuit 2, heating...
Coding in the delivered condition
d4:0
Heating curve level = 0
d5:0
The external operating program
changeover switches the operating
program to "Constant operation
with reduced room temperature" or
"Standby mode" (only for weather-
compensated control units)
d6:0
Heating circuit pump stays in con-
trol mode at signal "External block-
ing"
d7:0
Heating circuit pump stays in con-
trol mode at signal "External de-
mand"
d8:0
No operating program changeover
via EA1 extension
E1:1
Never adjust
E2:50
With remote control: No display
correction for the actual room tem-
perature (only for weather-com-
pensated control units)
E5:0
Never adjust
E6:...
Maximum speed of the variable
speed heating circuit pump in % of
the max. speed in standard mode.
Value is defaulted by boiler-specif-
ic parameters (only for weather-
compensated control units).
E7:30
Minimum speed of the variable
speed heating circuit pump: 30 %
of max. speed (only for weather-
compensated control units)
F1:0
Screed drying disabled (only for
weather-compensated control
units).
74
(cont.)
Possible change
d4:–13
Heating curve level adjustable from
to
13 to 40 (see page 46)
d4:40
d5:1
The external operating program
changeover switches to "Constant
operation with standard room tem-
perature" (subject to coding address
3A, 3b and 3C)
d6:1
Heating circuit pump stops at signal
"External blocking" (subject to cod-
ing addresses 3A, 3b and 3C)
d6:2
Heating circuit pump starts at signal
"External blocking" (subject to cod-
ing addresses 3A, 3b and 3C)
d7:1
Heating circuit pump stops at signal
"External demand" (subject to cod-
ing addresses 3A, 3b and 3C)
d7:2
Heating circuit pump starts at signal
"External demand" (subject to cod-
ing addresses 3A, 3b and 3C)
d8:1
Operating program changeover via
input DE1 at EA1 extension
d8:2
Operating program changeover via
input DE2 at EA1 extension
d8:3
Operating program changeover via
input DE3 at EA1 extension
E2:0
Display correction
to
to
E2:49
Display correction
E2:51
Display correction +0.1 K
to
to
E2:99
Display correction +4.9 K
E6:0
Maximum speed adjustable from 0
to
to 100 %
E6:100
E7:0
Minimum speed adjustable from 0 to
to
100 % of the maximum speed
E7:100
F1:1
Screed drying adjustable, with
to
choice of 6 temperature/time profiles
F1:6
(see page 122)
F1:15
Constant flow temperature 20
5 K
0.1 K
C
°