Control functions
(cont.)
Example using the settings in the delivered condition
C
60
D
B
50
40
30
30
20
10
A
0
6
00
Time in h
Fig.81
Start of operation with standard room temperature
A
Set boiler water or flow temperature in accordance
B
with the selected heating curve
Set boiler water or flow temperature in accordance
C
with coding address "FA":
50
C + 20 % = 60
C
°
°
D
Duration of operation with raised set boiler water
or flow temperature in accordance with coding
address "Fb":
60 min
Assigning heating circuits to the remote control
The assignment of heating circuits must be configured
during remote control commissioning.
Remote control affects the following heating circuit
Heating circuit without mixer A1
Heating circuit with mixer M2
Heating circuit with mixer M3
7
00
8
00
9
00
Function description
Configuration
Vitotrol 200A
Vitotrol 300A
Vitotrol 200 RF
Vitotrol 300 RF
H 1
Heating circuit 1
H 2
Heating circuit 2
H 3
Heating circuit 3
125