Electrical Wiring; Standard Electrical Wiring - Riello GS10 Installation, Use And Maintenance Instructions

Forced draught gas burner
Table of Contents

Advertisement

3.4

ELECTRICAL WIRING

3.4.1 STANDARD ELECTRICAL WIRING

Ionization probe
Electrode
Ignition transformer
Air pressure switch
Motor
Blue
White
Black
Blue
Black
Brown
Air damper actuator
NOTES:
– Do not exchange the neutral with the phase and connect exactly the
above wiring.
– Wires of min. 1 mm
ards and legislation).
– Carry out a safe earth connection.
– Verify that the burner stops by operating the boiler control thermostats and
that the burner locks out by separating the red ionisation probe lead con-
nector.
– The electric wiring carried out by the installer must be in compliance with
regulations in force in the Country.
2721
RMG 88.620A2
D4198
2
section. (Unless requested otherwise by local stand-
Connector
Control box
~
230V
GB
5
Burner earth
Suppressor
CARRIED-OUT
BY THE INSTALLER
ATTENTION
In the case of phase-phase
feed, a bridge must be fit-
ted on the control box ter-
minal
board
terminal 6 and the earth
terminal.
LEGEND
XP6 – 6 pole socket
50Hz
XP7 – 7 pole socket
X6 – 6 pin plug
X7 – 7 pin plug
B4 – Working signal
h1 – Hour counter
PG – Minimum gas pressure
switch
S3 – Remote lock-out signal
(230V - 0.5 A max.)
T6A – Fuse
TL – Limit thermostat
TS – Safety thermostat
V10 – Safety valve
V11 – Adjustment valve
between