11.1 CONNECTING THE ROOM THERMOSTAT

The connections in terminal block M1 are high voltage (230 V). Before making connections, make sure the appliance is
disconnected from the power supply. Respect polarity L (LIVE) - N (NEUTRAL).
To connect the Room Thermostat to the boiler, proceed as described below:
• switch off the boiler;
• access the terminal block M1;
• remove the jumper from the ends of contacts 1-2 and connect the wires of the Room Thermostat;
• switch on the boiler and make sure the Room Thermostat works correctly.

11.2 ACCESSORIES NOT INCLUDED IN THE SUPPLY

11.2.1 EXTERNAL SENSOR
To connect this accessory, see figure to side (terminals 4-5)
and the instructions supplied with the sensor.
SETTING THE "Kt" CLIMATE CURVE
When the external sensor is connected to the boiler, the
electronic board adjusts the flow temperature calculated
according to the set Kt coefficient. Select the required curve by
as indicated in the chart in annex SECTION
pressing
E for selecting the most appropriate one (00 to 90).
KEY TO CHART - "SECTION" E
Flow temp
11.2.2 CONNECTING TO A ZONE SYSTEM
To use this function, install the programmable relay electronic board supplied as an accessory.
KEY TO ELECTRICAL CONNECTIONS (see diagram in annex "SECTION" G at the end of this manual).
Z
Zone (1..n)
EV
Zone electrovalve
R
Relay
RT
Room thermostat
The boiler can manage a zone heating system. The Room Unit (wall-mounted) can be used to control one zone while normal
ambient thermostats can be used to control the other zones.
SYSTEM CONNECTIONS
• Connect the zone 1 valve/pump to terminals 1 - 3 of the relay board terminal block inside the boiler control box.
• Connect the Ambient Thermostat contact of the other zones to terminals 1-2 of terminal block M1 (CONNECTING THE
AMBIENT THERMOSTAT section).
Check that parameter P04=02. Set parameter P10 (SETTING PARAMETERS section).
Outside temp
33
7219623.01 (1-04/15)