Download Print this page

Reference Documents - GE J2007003L064 Quick Start Manual

Sps stackable slimline converter shelf

Advertisement

Information: Controller Default Voltage Settings and Ranges
Parameter
Converter Internal Selective High
Output Voltage Shutdown
High Output Voltage Major Alarm
High Output Voltage Minor Alarm
Output Voltage Set-Point
Low Voltage Alarm
Information: Converter Options
Converter
EP0300DC24TEZ
+24V Orange
Specifications and Application

Specifications and ordering information are in the

Equipment and subassembly ports: 1. are suitable for connection to intra-building or unexposed wiring or cabling;

Grounding / Bonding Network – Connect to an Isolated Ground Plane (Isolated Bonding Network) or an Integrated Ground Plane (Mesh-
Bonding Network or Common Bonding Network).

Installation Environment - Install in Network Telecommunication Facilities, OSP, or where NEC applies.

Battery return may be either Isolated DC return (DC-I) or Common DC return (DC-C).

Reference Documents

These documents are available at www.gecriticalpower.com.
Document
Title
850035894
Galaxy Pulsar Edge Quick Start Guide
CC848815341
Pulsar Edge Controller Family Product Manual
Slimline Power System Brochure
2
4
Range
Default
25.0 to 30.0V
29.0
25.0 to 30.0V
28.5
24.0 to 30.0V
27.0
23.0 to 27.2V
26.0
20.0 to 27.0V
23.0
Input DC
Voltage
Current
3
48Vdc
9A max
Slimline Power System Brochure
2. can be connected to shielded intra-building cabling grounded at both ends.
SPS J2007003 L064 - Quick Start Guide
Document 850047442 r01 2015 July
Output DC
Voltage
Current
24Vdc
11A
available at
www.gecriticalpower.com