INSTALLATION REQUIREMENTS

The installation must conform to the requirements of the author-
ity having jurisdiction or, in the absence of such requirements,
to the National Fuel Gas Code, ANSI Z223.1-latest edition.
This installation must also conform to the additional require-
ments in this Slant/Fin instruction book. Installation and service
to be performed by a qualified installer, service agency or the
gas supplier.
NATURAL GAS FIRED BOILER LOCATION—
Provide a level, solid foundation for the boiler. Location should
be as near the chimney as possible so that the flue pipe from
boiler to chimney is short and direct.
Automatic gas ignition system components shall be installed so
these components will not be subjected to dripping water during
installation or service.
WARNING
SPECIAL ATTENTION FOR LIQUEFIED PETROLEUM
(L.P.) PROPANE GAS-FIRED BOILER INSTALLATIONS
LPG appliances (boilers) shall be installed in accordance
with applicable provisions of NFPA 58 ( Liquefied Petroleum
Gas Code) latest edition for installations in US and
CAN/CGA B149.1 latest edition for installations in Canada.
Liquefied Petroleum (LP) propane gas is heavier than air
therefore Propane gas accumulate at floor level. If you sus-
pect a leak, do not attempt to operate boiler. A spark or
flame from the appliance (boiler) or other sources may ignite
the accumulated propane gas causing an explosion or fire.
It is recommended that inspections for gas leaks be per-
formed periodically by licensed professional and that leak
detection devices be installed as a further safety measure.

BOILER FOUNDATION

A. Provide a solid, level foundation, capable of supporting the
weight of the boiler filled with water, and extending at least
2" past the jacket on all sides. See dimensions of boilers,
page 2.
B. For installation on non-combustible floors only.*
C. If boiler is to be located over buried conduit containing elec-
tric wires or telephone cables, consult local codes or the
National Board of Fire Underwriters for specific require-
ments.
* The Combustible Floor Kit part number printed on the boiler rating plate is
the only one to be used when installing on combustible floors. The boiler
must not be installed on carpeting.

CHIMNEY REQUIREMENTS—

A. Galaxy boilers may be vented into a masonry vitreous tile-
lined chimney or UL LISTED type "B" venting system NOT
EXPOSED to the OUTDOORS below the roof line.
Venting and sizing of venting system must be in accordance
with Part 7, Part 11 and Appendix G of the National Fuel
Gas Code ANSI Z223.1, NFPA 54, -latest edition which will
be referred to as the National Fuel Gas Code. Local codes
apply.
If a masonry chimney is exposed to the outdoors on one or
more sides below the roof line (exterior chimney), ONE of
the following options apply:
1. Chimney must be re-lined with a UL LISTED metallic liner.
When this is done, the chimney will be considered NOT
exposed to the outdoors and the requirements of the
National Fuel Gas Code for NON-exposed chimneys
and/or local codes will apply.
2. If an exposed tile-lined chimney is to be used WITHOUT a
UL LISTED metallic liner, the boiler must meet the require-
ments of the National Fuel Gas Code:
B. If an existing boiler is removed from a common venting sys-
tem, the common venting system may be too large for prop-
er venting of the remaining appliances connected to the
common vent. Follow the test procedure shown in Appendix
"A" on page 15 of this manual to insure proper operation of
venting system and appliances.
C. Inspect for proper and tight construction. Any restrictions or
obstructions must be removed. An existing chimney may
require cleaning.
D.Chimney or vent must extend at least 3 feet above its pas-
sage through a roof and at least 2 feet above any ridge within
10 feet of the chimney.