Troubleshooting
2.
- On this mode the controller will ignore the manual address number set on the rotary switch on the indoor PCB.
2.
- To confirm the indoor address number assigned by this mode, use "TEST MODE" and the address number will be displayed on
the LED display on the indoor unit.
I In case of MANUAL ADDRESSING mode. (SW02-1:OFF)
2.
I
2.
Checking the address number correctly on each indoor unit PCB.
I
2.
- "PIPE CHECK MODE" is also able to use.
G If Error code is displayed on indoor or outdoor LED, check as follows;
I
1. Confirm if SW01 setting number and the number of indoor unit installed are
the same.
I
2. If some indoor unit has no power, confirm power cable connection,
especially miss-wiring between communication cable and power cable.
I
3. If error code E101 or E185 is displayed on indoor unit LED, check
communication wire and power wire connection.
I
4. If error code E460 is displayed on outdoor unit LED, AC power line could be
connected to outdoor communication terminal, F1 & F2. So check the wiring
not only communication line but also power line.
I
5. If error code E401, E404 or E416 is displayed on outdoor unit LED, check
PIPE connection also. Because gas flow to a different indoor unit will case
these error.
I
6. In case of communication error by wrong wiring on one indoor unit, all indoor
units display a error code. In this case, correction at the wrong point could
solve all indoor unit error display.
90