Download Print this page

Siemens ADM-Q12 Installation Manual page 3

Motion detector
Hide thumbs Also See for ADM-Q12:

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
en
Instruction
ADM-Q12 motion detector
The detector detects movement in the
room under surveillance
an alarm.
It responds most sensitively to movement
in the directions indicated by arrows
7
B / D. The back tamper recognizes if
the detector is removed with force.
Prerequisites
The detector should be installed by peo-
ple with specialist knowledge and in com-
pliance with valid regulations.
The detector is only intended
for indoor use. Note the posi-
tioning instructions
Opening the detector
1. Check the scope of delivery
2. Slide up the screw-on cover
loosen the screw
2
B.
3. Pull the housing front
2
C.
Fitting the detector
1. Fit the mounting base
- Define type of fastening
refer to mounting bracket option)
- Break open three fixing holes.
- Break open aperture for cable
feedthrough
4
D.
- Fit mounting base at the proposed
height.
-
The mounting base should be
secured using two screws
4
A, B and the back tamper
with one screw
2. Wire the power supply, alarm and
tamper connections according to the
options provided by the panel
Please note the end-of-line
usage guidelines for simplified
installation using the end-of-
line (EOL) concept
D back onto mounting
3. Fold front
2
base
2
C and secure with screw
Slide down screw-on cover
Programming
To adjust the settings to the application,
7
and initiates
move the jumpers into the corresponding
positions:
LED on / off
LED
AUTO
ON
LED
AUTO
ON*
* factory setting
PIR sensitivity
PULSE
1P*
6
.
2P
PULSE
1P
2P
1
.
A and
2
* factory setting
Pet immunity
2
D off the base
PET
12kg*
30kg
2
C as follows:
PET
4
A / B. (also
12kg
30kg
* factory setting
Sensitivity setting
-
*
* factory setting is the middle position
(12-meter field of vision)
4
C.
Walk test
Move the LED jumper
move the alarm control panel to walk test
8
.
mode. Look at the LED for verification
Run the walk test for alarm triggering in
the whole detection area
tor.
5
E /
9
.
Options
Narrow angle lens kit AO-C25
The kit enables the detection area cov-
2
B.
erage to be defined to a narrow angle as
2
A.
shown in
Loosen the lens currently at position
and remove this from the detector. Insert
adapter
down narrow angle lens.
5
A
LED only indicates motion in
walk test mode.
LED lights up when detecting
motion. *
5
B
High sensitivity, for quiet envi-
ronments.*
Low sensitivity, for busy envi-
ronments.
5
C
Suppresses alarm for pets up
to a weight of 12 kg.*
Suppresses alarm for pets up
to a weight of 30 kg.
5
D
+
Turn potentiometer (5D)
into the position required to
adjust detector to room size
and field of vision.
5
A to ON or
of the detec-
7
7
D.
3
C into detector and press
- 3 -
White light filter AO-WL10k
The white light filter is needed for applica-
tions with extreme white light interference
(> 4000 lux).
Loosen the lens currently at the positions
shown in
5
F and remove from the detec-
tor. Insert adapter
3
press the lens back down.
Wall & ceiling mounting brackets
The mounting brackets AZ-MBG2
(ceiling
10
B and wall
be used to swivel the detector ± 45°.
Technical data
Detection area
coverage
wide angle
7
B
Detection area
coverage
narrow angle
7
D
Connections
Supply voltage
Max. ripple
Power consumption
Current limit
Alarm output
Alarm holding time
Tamper contact
Control input
Self test – Fault
.
Warm up period
Pet immunity
EMI rejection up to
2GHz
Operating
temperature
Storage
temperature
Air humidity
5
F
EN 60721
Type of housing
protection
EN 60529
EN 50102
en
B into detector and
10
10
A
10
C mounting) can
12 m
20 m
Power supply
(2x)
Alarm (2x)
Tamper (2x)
(2- or 4-wire con-
nections can be
produced with the
EOL module)
9.6 ... 16 V
DC
(12 V
nominal)
DC
1 V
SS
Max. 17 mA
Max. 0.9 A
Opens during
alarm
2 ... 3 s
Opens during
alarm
Walk test
(on: +12V)
Red LED: on
Alarm relay: open
60 ± 5 s
< 12 kg
< 30 kg
> 10 V/m
-10 °C ... +50 °C
-20 °C ... +60 °C
< 85 % RH
not condensing
IP41 / IK02

Advertisement

loading