Plena 24 VDC Battery Charger | Installation and User Instructions | Equipment
3.3

External connections

3.3.1

Battery

The battery charger has 2 screw terminal connections to
the battery. Connect In + to the plus terminal of the
battery, connect the In - to the minus terminal of the
battery (see example in figure 3.5).
Caution
Always connect the batteries in series as shown
in figure 3.5. The total sum of the batteries must
equal 48 Volts. Only use batteries of equal
voltage, capacity and type.
figure 3.5: Connecting batteries to charger (example)
3.3.2

Back-up power connection

The battery charger has 2 screw terminal for connecting
to the Voice Alarm System or public address system.
Connect Out + to the plus terminals of the system
components, connect the Out - to the minus terminal of
the system components.
It is recommended that this back-up power connector is
not used for the Remote Control Panels or volume
overrides. Use the 24V DC output connectors.
Refer to 3.3.4.
Bosch Security Systems | 2006-11 | 9922 141 50781 en
-
+
-
+
3.3.3

Temperature sensor

The battery charger has one connector for a
temperature sensor, which is supplied with the battery
charger.
To improve the lifetime of the battery, applied voltages
and current are temperature dependant; therefore,
connect the sensor in such a way that a good thermal
reading is possible. For example, you can either connect
the sensor to the battery tray, or place it between two
batteries (see figure 3.6). If the temperature sensor is not
being used, the slide switch for the temperature sensor
should be set to off.
-
figure 3.6: Connecting the temperature sensor