Specifications - Fujitsu AUYA45LCLU Service Manual

Hide thumbs Also See for AUYA45LCLU:
Table of Contents

Advertisement

SPECIFICATIONS

ELECTRICAL DATA
TYPE
INDOOR UNIT
OUTDOOR UNIT
COOLING CAPACITY
HEATING CAPACITY
POWER SOURCE
RUNNING CURRENT
INPUT WATTS
E.E.R.
STARTING CURRENT
MOISTURE REMOVAL
AIRCIRCULATION INDOOR
AIRCIRCULATION OUTDOOR
MAXIMUM CURRENT
FAN MOTOR
Discrimination
High speed
Med speed
INDOOR UNIT
Low speed
Quiet
Discrimination
OUTDOOR UNIT
Upper fan
Lower fan
NOISE LEVEL
High speed
Med speed
INDOOR UNIT
Low speed
Quiet
Cooling
OUTDOOR UNIT
Heating
DIMENSIONS
DECORATION PANEL H x W x D
INDOOR UNIT
OUTDOOR UNIT
WEIGHT
DECORATION PANEL Gross / Net
INDOOR UNIT
OUTDOOR UNIT
2009.02.25
Cooling & Heating
AUYA45LCLU
AOYA45LBTL
12.5 kW
14.0 kW
230 V 50 Hz
Cooling
17.0 A
Heating
16.5 A
Cooling
3.89 kW
Heating
3.77 kW
Cooling
3.21 kW/kW
Heating
3.71 kW/kW
15 A
4.5 L/hr
1,900 m3/hr
6,600 m3/hr
20.0 A
MFF-54TVM
690 r.p.m.
610 r.p.m.
550 r.p.m.
470 r.p.m.
MFE-60TVT
850 r.p.m.
750 r.p.m.
46 dB
42 dB
40 dB
36 dB
55 dB
56 dB
50 x 950 x 950 mm
H x W x D
288 x 840 x 840 mm
H x W x D
1,290 x 900 x 330 mm
8.5 kg / 5.5 kg
Gross / Net
33 kg / 27 kg
Gross / Net
107 kg / 98 kg
COMPRESSOR AND REFRIGERANT
TYPE
DISCRIMINATION
WEIGHT (with oil)
REFRIGERANT TYPE
PRECHARGED REFRIGERANT
MAX PIPE LENGTH
MAX PIPE HEIGHT
Pipe length
FULL CHARGE
ADDITIONAL CHARGE
1
Hermetic type, Inverter,
4 poles, 3 phase,
DC motor, Twin Rotary
DA420A3F-21ZA
23.7 kg
R410A
3,350 g
50 m
30 m
20 m
3,350 g
30 m
3,850 g
40 m
4,350 g
50 m
4,850 g
50 g/m

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aoya45lbtl