Midea M2OC-14HRDN1 Technical & Service Manual page 22

Multi split type, heat pump air conditioners r410a multi dc inverter
Hide thumbs Also See for M2OC-14HRDN1:

Advertisement

1.
If the compressor frequency keeps lower than RECOILINFRE for Te minutes,the AC will rise the
frequency to RECOILFRE for Tf seconds and then resume to former frequency.For M4OC-36HRDN1-Q,
RECOILINFRE=45Hz, RECOILFRE=48Hz,Te=120,Tf=180; For M5OA-36HRDN1-Q, RECOILINFRE=45Hz,
RECOILFRE=48Hz, Te=90,Tf=100; For other models, RECOILINFRE=50Hz, RECOILFRE=62Hz,
Te=120,Tf=180.
2.
During the Tf seconds, the EXV and indoor units keep the current running mode(except
M5OA-36HRDN1-Q model), the frequency will not be limited by the compressor discharge temp.and the
current.For M5OA-36HRDN1-Q model,the EXV will keep 300p while the indoor units will keep the current
running mode.
3.
If the outdoor ambient is higher than 15℃ during the oil return,the AC quit oil return.
7.5.9 Compressor preheating functions
----Preheating permitting condition:
If T4(outdoor ambient temperature)<3
seconds or if T4<3
and compressor has stopped for over 3 hours, the compressor heating cable will
work.
----Preheating mode:
A weak current flow through the coil of compressor from the wiring terminal of compressor, then the
compressor is heated without operation.
----Preheating release condition:
If T4≧5
or
the compressor starts running, preheating function will stop.
7.5.10 Compressor crankcase heater
When T4<3℃ and the compressor is not running,the crankcase heater will be active.
When T4≧5℃ or the compressor starts up,the crankcase heater will stop work.(For M5OA-36HRDN1-Q,T4
≧8℃)
and the machine connects to power suppl
ODMI-1103-A
y no longer than 5