7.4.6 Opening degree of electronic expansion valve:
Opening degree equals the display data times 8
7.5 Protection
7.5.1 Three minutes delay at restart for compressor.
7.5.2 Temperature protection of compressor discharge.
When the compressor discharge temp. is getting higher, the running frequency will be limited as below
rules:
----If 102℃<T5<115 , decrease the freq
---If T5>115℃ for 10 seconds, the compressor will stop and restart till T5<90℃.
7.5.3 Under voltage protection
Mode
VOLLIMT1(V)
M2OC-14HRDN1
220
M2OC-14HRDN1-Q
220
M2OC-18HRDN1
230
M2OC1-18HRDN1-Q
230
M3OC1-21HRDN1-Q
245
M3OC-27HRDN1
245
M3OC1-27HRDN1-Q
245
M4OC-24HRDN1-Q
245
M4OC-27HRDN1
221
M4OC1-27HRDN1-Q
221
M4OC-36HRDN1-Q
200
For M5OA-36HRDN1-Q,
uency to the lower level every 2 minutes till to F1.
VOLTAGE
VOLLIMT1
VOLLIMT2
VOLLIMT3
VOLLIMT2(V)
VOLLIMT3(V)
200
80
200
80
200
80
200
120
220
80
220
80
220
120
220
120
210
80
210
80
185
80
VOLTAGE
VOLT_RST1_ADD
VOLT_LTM1_ADD
VOLT_RST2_ADD
VOLT_LTM2_ADD
VOLREL1
No limit
VOLFRE1
VOLREL2
VOLFRE2
VOLREL3
Off
VOLREL1(V)
VOLREL2(V)
250
210
250
210
260
210
260
210
265
240
265
240
265
240
265
240
260
225
260
225
210
195
No limit
VOLT_LTM_FREQ1_ADD
VOLT_LTM_FREQ2_ADD
VOLREL3(V)
VOLFRE1(Hz)
100
62
100
62
100
62
135
62
100
78
100
78
135
78
135
78
100
62
100
53
100
54
ODMI-1103-A
VOLFRE2(Hz)
54
54
54
54
45
45
45
45
54
44
42