Code 2
(cont.)
Coding in the delivered condition
72:0
DHW circulation pump
"ON" according to time
program
73:0
DHW circulation pump
"ON" according to time
program
General
76:0
Without LON communi-
cation module
77 :1
LON user number
79:1
Control unit is fault man-
ager
7b:1
Send time via LON
7F:1
Detached house
80:1
With 5 s delay for fault
message; message is
displayed if fault is
present for at least 5 s
81:1
Automatic summer/win-
ter time changeover
Possible change
72:1
"OFF" during DHW heating
to the second set value
72:2
"ON" during DHW heating
to the second set value
73:1
During the time program
to
1x/h "ON" for 5 min
73:6
up to 6x/h "ON" for 5 min
73:7
Permanently "ON"
76:1
With LON communication
module (automatic recog-
nition)
77 :2
LON subscriber number,
to
adjustable from 1 to 99:
77 :99
1 - 4 = Boiler
5 = Cascade
10 - ... = Vitotronic 200-H
99 = Vitocom
Note
Allocate each number only
once.
79:0
Control unit is not fault
manager
7b:0
Do not send time via LON
7F:0
Apartment building.
Separate adjustment of
holiday program and time
program for DHW heating,
as option
80:0
Without time delay
80:2
Time delay adjustable from
10 to 995; 1 step ≙ 5 s
to
80:199
81:0
Manual summer/winter
time changeover
81:2
Radio clock module is
automatically detected
81:3
Accept time via LON
Codes
45