Viessmann Vitoladens 300-C Service Instructions Manual page 39

Oil condensing boiler
Hide thumbs Also See for Vitoladens 300-C:
Table of Contents

Advertisement

Code 1
(cont.)
Coding in the delivered condition
User no.
77:1
LON user number
DHW priority A1/M2
A2:2
Cylinder priority control
for heating circuit pump
and mixer
Summer econ. A1/M2
A5:5
With heating circuit pump
logic function
Min. flow temp. A1/M2
C5:20
Electronic minimum flow
temperature limit 20 °C
Max. flow temp. A1/M2
C6:74
Electronic maximum flow
temperature limit set to
74 °C
Slope A1/M2
d3:14
Heating curve slope =
1.4
Level A1/M2
d4:0
Heating curve level = 0
Possible change
77:2
LON subscriber number,
to
adjustable from 1 to 99:
77:99
1 - 4 = Boiler
5 = Cascade
10 - ... = Vitotronic 200-H
99 = Vitocom
Note
Allocate each number
only once.
A2:0
Without cylinder priority
applicable to heating circuit
pump and mixer
A2:1
Cylinder priority only appli-
cable to mixer
A2:3
Modulating priority applied
to
to mixer; i.e. the heating cir-
A2:15
cuit receives a reduced
amount of heat
A5:0
Without heating circuit
pump logic function
C5:1
Minimum limit adjustable
to
from 1 to 127 °C
C5:127
C6:1
Maximum limit adjustable
to
from 1 to 127 °C
C6:127
d3:02
Heating curve slope adjust-
to
able from 0.2 to 3.5 (see
d3:35
page 30)
d4:–13
Heating curve level adjust-
to
able from –13 to 40 (see
d4:40
page 30)