Biasi Inovia ERP Series Service Manual page 23

G.c. appl. no. 47-583-38, 47-583-39, 47-583-40, 41-583-30
Table of Contents

Advertisement

figure 9 .10
6 In order to pass from a parameter to another press c.h. set
keys (A or C) at the same time until p 02 are displayed on
the display, indicating the entry in the "parameter 02" and the
value of parameter (Figure 9.11)
figure 9 .11
7 Repeat the previous steps in order to display the parameter's
setting or to switch to the following
figure 9 .12
To reset the boiler to the normal operation press the key B (Figure
9.5) for 10 second or turn off the electricity supply to the boiler.
MAIN ElEctroNIc coNtrol/IgNItIoN p.c.b.
a
c
a
c
b
important: at the end of the setting operation it is important
to fill/update the table in the installation manual see chapter
cOmmissiOninG section: setting record .
parameter
Boiler type (to be up-
dated with the complete
range)
Type of water sensors
(C.h. / d.h.w.)
Pump speed
Zone valve setting
Room Thermostat /
Remote Control
Gas type
Not used
C.h. flow max
temperature °C
Factory parameters
reset
lcd
values (set)
p 01
00 = No power Er 99
35 = Inovia 25C ERP
36 = Inovia 30C ERP
37 = Inovia 35C ERP
41 = Inovia 25S ERP
p 02
00 =
+
+
+
+
+
+
01 =
+
+
+
+
+
+
factory set
+
02 =
+
+
+
+
+
+
03 =
+
+
+
+
+
00 =
01 =
p 03
00 =
(2) Max
factory set
01 =
(1) Med
02 =
Self regulat.
p 04
00 = No (factory set)
01 = Z1 with R.T., Z2
with R.C., Max. c.h.
flow temperature
02 = Z1 with R.T., Z2
with R.C., Min. c.h.
flow temperature
p 05
00 = G20 Natural
01 = G25
02 = --- --- --- ---
03 = --- --- --- ---
04 = G30 Butane
05 = G31 Propane
p 06
p 07
85÷45 (factory set 85 °C)
p 08
00 = No reset
04 = All parameters
return to factory set
with the exclusion of
P 01 and P 05
39 = All parameters return
to factory set included Pr
01 and Pr 05
- 23 -