Mitsubishi Electric MFZ-KA09NA Installation Manual page 6

Floor type air conditioners
Hide thumbs Also See for MFZ-KA09NA:

Advertisement

Available languages

Available languages

I
2=8. CONNECTING WIRES FOR iNDOOR UNIT
Note: When the indoor unit is powered from the outdoor unit, depending
on local code, a disconnect
switch needs to be installed to a power supply circuit.
1 ) Remove the electrical
cover.
2) Remove the conduit plate.
3) Attach the conduit pipe to the conduit plate with the lock nut. The indoor/outdoor
unit connecting wire (A) appearing
from the inside of conduit pipe should be less
than 7/8 in. (23 mm). (Fig. 1)
4) Process the end of ground wire (Fig. 2). Connect it to the ground terminal of the electrical
parts box.
5) Process the end of indoor/outdoor
unit connecting wire (A) (Fig. 2). Attach it to the terminal block. Be careful not to make mis-wiring. Attach the wire to the terminal
block securely so that its core cannot be seen, and no external force affects the connecting
section of the terminal block.
6) Firmly tighten the terminal screws. After tightening,
verify that the wires are tightly fastened.
7) Reinstall
the conduit
plate.
8) Reinstall
the electrical
cover.
Remark:
*
A disconnect
switch (15A
MAX) is required.
Check the local code.
** Use a ring tongue
termF
nal in order to connect a
ground wire to terminal.
Power supply
208/230 VAC,
1 phase 2 wires.
60 Hz
INDOOR UNIT
-, Grounding
! Termina_ block._
terminaF*
I_!
i
i
/
Disconnect
"
4 _t -
switch*
208/230 VAC S'mi_
i
1 phase, 60 Hz
OUTDOOR UNIT
.............
'-------i---i:
....
Ground
Grouding terminaF*
_
Conduit
plate
LeSs than 7/8 in,
(23 ram)
k nut
nduit pipe
Fig. 1
19/32 in,
1_3/8 in.
__Z_
(15 ram)
(35 ram)
Lead__
Fig. 2
Screw
Electrical
cover
Terminal
block
Electrical
box
Lock nut
Conduit plate
Grounding
terminal
pipe
Indoor/outdoor
unit
connecting
wire (A)
Connect
wires
to the appropriate
terminals
For future
servicing,
leave
some
slack
in the connecting
wires.
/I
/
2-9. CONNECTING AN INTERFACE (MAC=397/399 IF-E, option) TO THE AiR CONDITIONER
, Connect an interface to the indoor control P.C. board of an air conditioner
with a connecting
cable.
, Cutting or extending the connecting
cable of the interface results in defects
in connecting.
Do not bundle the connecting
cable together with power
supply cord, indoor/outdoor
connecting wire, and/or earth wire. Keep as
much distance as possible between the connecting
cable and those wires.
, The thin part of the connecting cable should be stored and placed where
customers
cannot touch it.
Thin part of the connecting cable.
Place this part where customers
Room air
cannot touch it.
I
Indoor control
CN105
P.C. board
Main body of an interface
*_@
Connector
Thick part of the connecting
cable
1 ) Remove the electrical
cover.
2) Join the connecting
cable to CN105 on the indoor control P.C. board.
3) Hook the connecting
cable as shown in the figure.
4) Attach the cable clamp provided with Interface to the thick part of the connecting
cable with a screw
4x16 as shown in the figure.
5) Reinstall the electrical cover. Be careful not to catch the thin part of the connecting
cable in the cover.
Fix the connecting cable at the prescribed position
]
securely.
J
Incorrect installation
may cause electric shock, fire,
and/or malfunction
,CN105
4) Cable clamp
Cord clamp
3) Hook
En-5