Mitsubishi SRK63ZM-S Technical Manual page 88

Inverter wall mounted type residential air-conditioners (split system, air to air heat pump type)
Table of Contents

Advertisement

Functions of CNT connector
It is available to operate the air conditioning unit and to monitor the operation status with the external control unit (remote display)
by sending the input/output signal through CNT connector on the indoor control PCB.
①Connect a external remote control unit (procured locally)
to CNT terminal.
②In case of the pulse input, switch OFF the DIP switch
SW2-1 on the interface PCB.
③When setting operation permission/prohibition mode,
switch OFF the DIP switch SW2-3 on the interface PCB.
Input/
Function
Output
Output 1
Operation output
Output 2
Heating output
Output 3
Compressor operation output
Output 4
Malfunction output
SW2-1
Input/
Function
Output
Setting
ON* Level input
External
Input
control
input
OFF
Pulse input
Connection of super link E board
Regarding the connection of super link E board, refer to the instruction manual of super link E board.
For electrical work, power supply for all of units in the super link system
must be turned OFF.
①Switch ON the DIP switch SW2-2 (Factory setting: ON) on the interface PCB.
Caution:Wireless remote control attached to the indoor unit can be used in parallel, after
connecting the wired remote control. However, some of functions other than
the basic functions such as RUN/STOP, Temperature Setting, etc. may not work
properly and may have a mismatch between the display and the actual behavior.
②Wiring connection between the interface and the super link E board.
Interface side
Terminal
Y
block for
Super link
X
E board
③Clamp the connection cables with cable clamps.
Output signal
Content
Relay
ON/OFF
XR
ON
During air-conditioner operation
1
XR
ON
During heating operation
2
XR
ON
During compressor running
3
XR
ON
During anomalous stop
4
SW2-3
Input signal
Setting
Level/Pulse
XR
5
OFF→ON
External input
ON*
ON→OFF
Level
OFF→ON
Operation permission
OFF
Operation prohibition
ON→OFF
OFF→ON
External input
ON*
Pulse
OFF→ON
Operation permission
OFF
Level
ON→OFF
Operation prohibition
* Factory setting
Super link E board
Y
Terminal
block for
X
iterface
Note (1) 0.3mm
Indoor units
Do not use the length over 2 meter
control box
Red
+12
1 1
Black
2
2
XR1
CNT
Yellow
XR2
3
3
(Blue 6P)
Blue
4
4
XR3
Brown
XR4
5
5
Orange
6
6
XR5
PCB (Printed Circuit Board)
●XR
1~4
is a DC 12/24V or AC 220~240V relay
●XR
5
●CNT connector (local) maker, model
Connector
Terminals
Air-
Operation by
Conditioner
Remote Control
Content
ON
OFF
Allowed
OFF
Not allowed
OFF
OFF→ON
ON→OFF
Allowed
ON
OFF
Not allowed
Names of recommended signal wires
No.
Shielded wire
1
Vinyl cabtyre round cord
2
3
Vinyl cabtyre round cable
4
Vinyl insulated wirevinyl sheathed cable for control
Within 200 m 0.5 mm
Within 300 m 0.75 mm
Within 400 m 1.25 mm
Within 600 m 2.0 mm
87
-
-
'13 • SRK-T-142
0.75mm
2
×2m
2
×2m
Butt splice
(Application coverage
0.75~1.25mm
White
XR1
Black
Yellow
XR2
Blue
XR3
XR4
Brown
Orange
XR5
Orange
Remote start / stop button or timer point
Remote start/stop kit (procured locally)
are for the DC 12V relay
Molex
5264-06
Molex
5263T
DIP switch
(SW2-2)
2 cores
2
2 cores
2
2 cores
2
2 cores
2
)
2
Common
Output 1
Output 2
Output 3
Output 4
Input
power
DIP switch
(SW2-3)
DIP switch
(SW2-1)