12. Installation Instruction
(CS-E28PKES CU-E28PKE only)
12.1 Select the Best Location
12.1.1
Indoor Unit
•
Do not install the unit in excessive oil fume area
such as kitchen, workshop and etc.
•
There should not be any heat source or steam
near the unit.
•
There should not be any obstacles blocking the air
circulation.
•
A place where air circulation in the room is good.
•
A place where drainage can be easily done.
•
A place where noise prevention is taken into
consideration.
•
Do not install the unit near the door way.
•
Ensure the spaces indicated by arrows from the
wall, ceiling, fence or other obstacles.
•
Recommended installation height for indoor unit
shall be at least 2.5 m.
12.1.2
Outdoor Unit
•
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from
the condenser is not obstructed.
•
There should not be any animal or plant which
could be affected by hot air discharged.
•
Keep the spaces indicated by arrows from wall,
ceiling, fence or other obstacles.
•
Do not place any obstacles which may cause a
short circuit of the discharged air.
•
If piping length is over the [piping length for
additional gas], additional refrigerant should be
added as shown in the table.
Example: For E28***
If the unit is installed at 15 m distance, the quantity of
additional refrigerant should be 150 g .... (15-10) m ×
30 g/m = 150 g.
12.1.3
Indoor/Outdoor Unit Installation
Diagram
•
This illustration is for explanation purposes only.
The indoor unit will actually face a different way.
71