Honeywell Intelliguard 9000 Installation Instructions Manual page 22

Hide thumbs Also See for Intelliguard 9000:
Table of Contents

Advertisement

INTELLIGUARD 9000™
INTELLIGUARD CONTROL PANEL 1
INTELLIGENT COMMUNICATIONS
PROCESSOR II (ICP II) 8003-331
COM 3
12V
DTR
DIR
Rx
Tx
IN
OUT
+
DS3
RS-232
1 2 3 4 5 6 TB2
TB1
3 2 1
U1
U2
S1
4
PSEUDO
TB2
1
RS-232 TO
UNIT 1
RS-485
1 2 3 4
INTERFACE
(RRI)
8003-322
ADDITIONAL BAUD RATES
REMOTE PROG.
NONE
4800
NOTE: EBI SOFTWARE SUITE IS PRESENTLY LIMITED TO 1200 AND 2400 BAUD.
= DON'T CARE
BIAS
E.O.L.R.
TERMINATION
1
SET THE SWITCHES ON UNIT 1 (FARTHEST FROM THE PC) FOR BIAS DISABLED (S1-1/S1-4 OFF) AND EOLR TERMINATION ENABLED (S1-2/S1-3 ON). ON
UNIT 4 ENABLE THE RS-485 TERMINATOR AND LINE BIAS. (THIS IS BASED ON THE ASSUMPTION THAT UNITS 1 AND 4 ARE EXTREME OPPOSITE DEVICES
WITH THE LONGEST CABLE LENGTH BETWEEN THEM, NOT NECESSARILY THE DEVICES THAT ARE PHYSICALLY LOCATED THE FARTHEST APART.)
2
SET THE SWITCHES OF UNIT 2 (AND ANY OTHER INTERMEDIATE UNITS) TO OFF.
3
NOTICE THAT THE DAT – AND DAT + CONNECTION MUST BE INVERTED AT UNIT 4. THIS IS REQUIRED SINCE THE RRIs FOLLOW THE I9000
STANDARD WHICH IS THE REVERSE OF THE INDUSTRY STANDARD.
4
REFER TO APPENDIX C FOR IC109 SETUP INFORMATION.
NOTES:
A MAXIMUM OF FOUR RS-485 DEVICES CAN BE CONNECTED IN A MULTI-DROP CONFIGURATION INCLUDING THE RS-485 BLACK BOX CONVERTER.
THE GROUND BETWEEN UNITS 1 (TB2-1), 2 (TB2-1) AND 3 (TB2-1) ARE NOT NECESSARY IF A GROUND REFERENCE IS PROVIDED THROUGH OTHER
MEANS. ONLY ONE GROUND REFERENCE MUST BE USED TO PREVENT GROUND LOOPS.
IN THE CONFIGURATION SHOWN, THE INTELLIGUARD CONTROL PANELS ONLY COMMUNICATE WITH THE EBI PC. THE INTELLIGUARD CONTROL PANELS
DO NOT COMMUNICATE PEER-TO-PEER WITH EACH OTHER.
Fig. 22. EBI RS-485 multi-drop wiring (using black box RS-232 to RS-485 Converter on the PC side).
74-3047—1
INTELLIGUARD CONTROL PANEL 2
INTELLIGENT COMMUNICATIONS
PROCESSOR II (ICP II) 8003-331
DS3
RS-232
TB1
3
2
1
ON
2
UNIT 2
1 2 3 4
SUPPORTED BAUD RATES - 75, 150, 300, 600, 1200 & 2400
FIRMWARE
PART NO.
SMP/EBI ORBIX
NONE
8950-100
4800
8950-109
BIAS AND TERMINATION
S1
4
3
2
DISABLE
ENABLE
DISABLE
ENABLE
COM 3
12V
DTR
DIR
Rx
Tx
IN
OUT
+
1 2 3 4 5 6 TB2
3 2 1
U1
U2
S1
4
3
2
1
ON
PSEUDO
TB2
RS-232 TO
RS-485
INTERFACE
(RRI)
8003-322
SOFTWARE VERSION
I9000 XSM (SMP PROTOCOL)
I9000 EBI ORBIX
AC POWER IN
UPS
AC POWER OUT
1
POSITION
OFF
ON
OFF
ON
OFF
ON
OFF
ON
22
INTELLIGUARD CONTROL PANEL 3
INTELLIGENT COMMUNICATIONS
PROCESSOR II (ICP II) 8003-331
COM 3
12V
DTR
DIR
Rx
Tx
IN
OUT
+
DS3
RS-232
1 2 3 4 5 6 TB2
TB1
3 2 1
U1
U2
S1
4
3
2
1
ON
PSEUDO
TB2
2
RS-232 TO
UNIT 3
RS-485
1 2 3 4
INTERFACE
(RRI)
8003-322
4
LEVER
UNIT 4
3
RS-232 TO RS-485
CONVERTER.
BLACK BOX IC109
4
1400609R-047900
PC SIDE
1
3
2
5
EBI PC
WITH RS-232 PORT (TYPICALLY
COM 1 OR DIG1 ACCELPORT.)
M14488A
S1
3
2
1
ON