Load Impedance:
Isolation:
Range Selection Method:
LOOP CONTROL
Automatic Tuning Types:
Proportional Bands:
Reset (Integral Time Constant):
Rate (Derivative Time
Constant):
Manual Reset (Bias):
Deadband/Overlap:
ON/OFF Differential:
Auto/Manual Control:
Cycle Times:
Setpoint Range:
ALARM CONTROL
Maximum Number of Alarms:
Max. No. of Outputs Available:
B-8
0 - 20mA: 500
maximum
4 - 20mA: 500
maximum
0 - 10V: 500
minimum
0 - 5V: 500
minimum
Isolated from all other inputs and outputs.
Link jumper or DIP.
Pre-Tune
0 (OFF), 0.5% - 999.9% of input span at 0.1%
increments.
1s - 99min 59s and OFF
0 (OFF) - 99 min 59 s.
Added each control algorithm execution.
Adjustable in the range 0 - 100% of output
power (single output) or –100% to +100% of
output power (dual output).
–20% to +20% of Proportional Band 1 +
Proportional Band 2.
0.1% to 10.0% of input span.
User-selectable with "bumpless" transfer into
and out of Manual Control.
Selectable from
s to 512 secs in binary steps.
1
2
Limited by Range Maximum and Range
Minimum.
Two "soft" alarms.
Up to two outputs can be utilised for alarm
purposes.