Time2
Time conditions(Meet the following conditions)
1.Running in heating mode
2. T4<3℃
3. Compressor is on
4. T3≤TempEnterDefrost_ADD ℃
Cleared conditions (Meet any one of the following conditions)
1. Compressor is off and T3>TempEnterDefrost_ADD +2℃ last for 20 minutes
2. Running in cooling mode.
3. Compressor is off for 1 hour.
Condition of entry defrosting:
time1+ time2≥40 minutes, When defrosting is end,time1 and time2 are cleared.
Condition of ending defrosting:
If any one of following items is satisfied, defrosting will stop and the machine will turn to normal heating
mode.
① The defrosting time achieves 10min;
② T3 ≥15℃;
③ T3 ≥7℃ for 60seconds.
Defrosting action:
4-Way valve
Compressor
10S 30S
Indoor fan
Outdoor fan
PMV
Electrical Control System
no longer than 10min
TimeA
480P
10S
PMV running
8 mins with 300P
Electrical Control Function