Worcester Greenstar 12Ri Technical Information page 28

Ri series, cdi classic regular series regular gas-fired condensing wall mounted boiler range
Hide thumbs Also See for Greenstar 12Ri:
Table of Contents

Advertisement

Extension flue upwards and horizontal
using a second 90º bend
Maximum
length (mm)
Greenstar Ri series
100mm
2,600
1
125mm 11,000
1
Greenstar 30CDi Classic Regular
100mm
6,400
1
125mm 16,500
1
Greenstar 40CDi Classic Regular
100mm
4,500
1
125mm 10,500
1
Note: The short flue extension (100mm dia.) may be used
as an alternative to the standard extension as required up
to the maximum flue lengths stated (7 716 191 133).
Note: The maximum flue length must be reduced by the
following amounts for each bend used.
Greenstar Ri
– all size flues
45º bend
1m
90º bend
2m
28
Option 5
Components required
up to 3
2
up to 11
2
up to 6
2
up to 16
2
up to 4
2
up to 10
2
Greenstar CDi
Greenstar CDi
Classic Regular
Classic Regular
60/100mm flues
80/125mm flues
0.75m
1m
1.5m
2m
Extension flue upwards and horizontal
Maximum
length (mm)
1
Greenstar Ri series
1
125mm
9,000
Greenstar 30CDi Classic Regular
1
100mm
4,900
1
125mm 14,500
Greenstar 40CDi Classic Regular
1
100mm
3,000
1
125mm
8,500
Option 6
using a third 90º bend
Components required
1
up to 9
3
1
up to 5
3
1
up to 14
3
1
up to 2
3
1
up to 8
3
1
1
1
1
1