Ease of installation
The CondenseSure has been designed for ease of
installation in mind and is suitable for most boiler
applications. For maximum effectiveness it should
be installed immediately beneath the boiler where
it is clipped on to the boiler's heating flow pipe and
connected to its siphonic trap. If this is not practical,
the CondenseSure can be wall-mounted away from the
boiler and connected to a 32mm condensate discharge
pipe. However, this will sacrifice the benefit of warming
the condensate prior to discharge and therefore slightly
reduce its performance.
Siphon
trap
CondenseSure
A typical installation using CondenseSure
The CondenseSure installation parameters
The CondenseSure will protect an externally run condensate
discharge pipe from freezing for 48 hours at -15°C providing
the following installation parameters are met:
The externally run pipe length does not exceed 3 metres
There is a fall on the discharge pipe of at least 2.5 degrees
The discharge pipe diameter is not less than 32mm
in diameter.
Whilst it is not necessary to insulate the pipework it may
be a consideration if longer lengths or if lower external
temperatures are expected.
The CondenseSure
clips onto the
22mm heating
flow pipe using
the 'free' heat
to raise the
condensate
temperature.
External pipework
3000mm max.
2.5º fall min.
32mm OD pipe
Fitting to a regular boiler
1
6
7
1. Foam backing with double-sided tape
2. Siphon mounting screws
3. Siphon body
4. Foam insert (used with regular or system boilers)
5. Foam cover
6. CH flow pipe
7. CH return pipe Greenstar Ri only
Additional installation considerations include:
Keeping any external pipework as short as possible
Minimising the number of bends and connections
1.
Removal of burrs after cutting pipe
Removal of surplus solvent from the
interior of the pipe.
The CondenseSure has no working parts to breakdown,
does not use any energy and has no electrical connections,
so there is no Part P requirement.