Wiring Diagram - Daikin FUQ71BVV1B Technical Data Manual

Split sky air 4-way blow ceiling suspended cassette
Hide thumbs Also See for FUQ71BVV1B:
Table of Contents

Advertisement

8

Wiring diagram

8 - 1 Wiring diagram
FUQ71∼125B
Notes
1. D : Terminal
F : Connector
8
b : Protective earth (screw)
2.
: Field wiring
3. In case using central remote control, connect it to the unit in
accordance with the attached instruction manual.
4. X24A is connected when the infrared remote control kit is
being used.
5. Remote control model varies according to the combination
system, confirm technical materials and catalogs, etc. before
connecting.
6. Symbols show as follows Red:red, Blk:black, Ylw:yellow,
Org:orange, Gry:gray, Prp:purple, Blu:blue
7. Confirm the method of setting the selector switch (SS1, SS2)
by installation manual and engeneering materials, etc.
A1P
Printed circuit board
C1R
Capacitor (M1F)
HAP
Light emitting diode (service monitor green)
KAR
Magnetic relay (M1S)
KPR
Magnetic relay ((M1P)
M1F
Motor (indoor fan)
M1P
Motor (drain pump)
M1S
Motor (swing flap)
Q1M
Thermo switch (M1F embedded)
R1T
Thermistor (air)
R2T
Thermistor (coil)
10
• Indoor Units • R-410A • FUQ-BVV1B
To outdoor
unit
S1L
Float switch (M1A)
Receiver / display unit (attached to infrared remote controller)
S1Q
Limit switch (swing flap)
A2P
Printed circuit board
SS1
Selector switch (emergency)
A3P
Printed circuit board
T1R
Transformer (220-240V/22V)
BS1
Push button (on/off)
V1TR
Phase control circuit
H1P
Light emitting diode (service monitor red)
X1M
Terminal strip
H2P
Light emitting diode (service monitor green)
X2M
Terminal strip
H3P
Light emitting diode (service monitor red)
?
Signal receiver circuit
H4P
Light emitting diode (service monitor orange)
.
Signal transmission circuit
SS1
Selector switch (main/sub)
Wired remote control
SS2
Selector switch (wireless address set)
R1T
Thermistor (air)
SS1
Selector switch (main/sub)
• Split Sky Air • Indoor Units
Wired remote
control
Note) 4
Norm. Emerg.
Connector for optional parts
X35A
Connector (group control adapter)
X60A
Connector (interface adapter for sky air series)
X61A
In case of simultaneous
operation system.
Indoor unit
Indoor unit
(slave)
(master)
Infrared remote
control
Note) 4
Receiver / display unit
Control box
3D043746A

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fuq100bvv1bFuq125bvv1b

Table of Contents