Generac Power Systems Guardian 005240 Installation And Owner's Manual page 26

Hide thumbs Also See for Guardian 005240:
Table of Contents

Advertisement

Maintenance
4.11.2 RETURN TO SERVICE
To return the unit to service after storage, proceed as follows:
1.
Verify that utility power is turned off and that the AUTO/OFF/
MANUAL switch is set to OFF.
2.
Check the tag on the engine for oil viscosity and classification.
Verify that the correct recommended oil is used in the engine
(see the Engine Oil Recommendations section). If necessary,
drain and refill with the proper oil.
3.
Check the state of the battery. Fill all cells of unsealed bat-
teries to the proper level with distilled water. DO NOT USE
TAP WATER IN THE BATTERY. Recharge the battery to 100
percent state of charge, or, if defective, replace the battery.
See "Specifications," for type and size.
4.
Clean and wipe the entire generator.
5.
Make sure the 15A fuse is removed from the generator con-
trol panel. Reconnect the battery. Observe battery polarity.
Damage may occur if the battery is connected incorrectly.
6.
Open the fuel shutoff valve.
7.
Insert the 15A fuse into the generator control panel. Start the
unit by moving the AUTO/OFF/MANUAL switch to MANUAL.
Allow the unit to warm up thoroughly.
8.
Stop the unit by setting the AUTO/OFF/MANUAL switch to
OFF.
9.
Turn on the utility power to the transfer switch.
10. Set the AUTO/OFF/MANUAL switch to AUTO.
11. The generator is now ready for service.
If the battery was dead or disconnected, the exercise timer
must be reset.
24
NOTE:

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Guardian 005240 and is the answer not in the manual?

Questions and answers

Table of Contents

Save PDF