Intelligent photoelectronic smoke sensor

Advertisement

Quick Links

INSTALLATION AND MAINTENANCE INSTRUCTIONS
2951 Intelligent Photoelectronic
Smoke Sensor

Specifications

Operating Voltage Range:
Current:
LED Current:
Operating Humidity Range:
Operating Temperature Range:
Height:
Diameter:
Weight:

Before Installing

This sensor must be installed in compliance with the con-
trol panel system installation manual. The installation must
meet the requirements of the Authority Having Jurisdiction
(AHJ). Sensors offer maximum performance when installed
in compliance with the National Fire Protection Association
(NFPA); see NFPA 72, and all applicable codes, ordinances
and regulations.

General Description

Model 2951 is a plug-in type smoke sensor that combines a
photoelectronic sensing chamber with addressable-analog
communications. The sensor transmits an analog represen-
tation of smoke density over a communication line to a
control panel. The sensor's address is set by the Hand Held
Programmer (HHP ). An LED on the sensor is controlled by
the panel to indicate sensor status.
The Model 2951 requires compatible addressable com-
munications to function properly. Connect this sensor to
listed-compatible control panels only.
Spacing
System Sensor recommends spacing sensors in compliance
with NFPA 72. In low air flow applications with smooth
ceilings, space sensors 30 feet apart. For specific informa-
tion regarding sensor spacing, placement, and special ap-
plications, refer to NFPA 72 or the System Sensor Guide For
Proper Use of System Smoke Detectors, available at no
charge from System Sensor (P/N I56-407-XX).
D200-86-00
15 to 30 VDC
270 µ A Max. Communication active but not to device in blink mode
6.5 mA Continous ON
10% to 93% Relative Humidity, noncondensing
0° to 49° C (32° to 120° F)
1.95 inches (50 mm) installed in Base
4.0 inches (102 mm) installed in Base
2.96 oz. (92 g)
1
3825 Ohio Avenue, St. Charles, Illinois 60174

Wiring Instructions

All wiring must be installed in compliance with the Na-
tional Electrical Code, applicable local codes, and any spe-
cial requirements of the Authority Having Jurisdiction.
Proper wire gauges should be used. The installation wires
should be color-coded to limit wiring mistakes and ease
system troubleshooting. Improper connections will prevent
a system from responding properly in the event of a fire.
NOTE: The mounting base (B901) uses SEMS Plate termi-
nals and can accommodate 2 wires each. The 2
wires can differ by a maximum of 2 wire gauges.
Remove power from the communication line before in-
stalling sensors.
All wiring must conform to applicable local codes, ordi-
nances, and regulations.
1. Wire the sensor base (supplied separately) per the wir-
ing diagram, see Figure 1.
2. Prior to installation, address the sensor using the Hand
Held Programmer (HHP ). See Hand Held Programmer
instruction manual for proper operation.
3. Install the sensor into the sensor base. Push the sensor
into the base while turning it clockwise to secure it in
place.
A Division of Pittway
1-800-SENSOR2, FAX: 630-377-6495
I56-1321-00

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 2951 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for System Sensor 2951

  • Page 1 Improper connections will prevent a system from responding properly in the event of a fire. General Description Model 2951 is a plug-in type smoke sensor that combines a NOTE: The mounting base (B901) uses SEMS Plate termi- photoelectronic sensing chamber with addressable-analog nals and can accommodate 2 wires each.
  • Page 2 Figure 1: Remote Annunciator +R/A +IN/OUT +R/A +IN/OUT +R/A +IN/OUT CLASS A OPTIONAL WIRING A78-2665-01 4. After all sensors have been installed, apply power to the The sensor can be tested in the following ways: control unit and activate the communication line. A.
  • Page 3 Figure 2: Cleaning It is recommended that the detector be removed from its mounting base to facilitate cleaning. The detector is cleaned as follows: SENSOR COVER NOTE: Before removing the detector, notify the proper au- thorities that the smoke detector system is undergoing maintenance and will be temporarily out of service.
  • Page 4 NFPA 72 or at least once a year. Three-Year Limited Warranty System Sensor warrants its enclosed smoke detector to be free from de- ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please fects in materials and workmanship under normal use and service for a include a note describing the malfunction and suspected cause of failure.