Checklist - Bryant 311AAV Installation, Start-Up, Operating And Service And Maintenance Instructions

Deluxe induced-combustion 4-way multipoise furnace - series c
Table of Contents

Advertisement

THERMOSTAT SUBBASE
TERMINALS WITH
THERMOSTAT REMOVED
(ANITICIPATOR, CLOCK, ETC.,
MUST BE OUT OF CIRCUIT.)
10 TURNS
FROM UNIT 24-V
CONTROL TERMINALS
EXAMPLE: 5.0 AMPS ON AMMETER
10 TURNS AROUND JAWS
Fig. 54—Amp Draw Check With Ammeter
c. Unblock return air to permit normal circulation.
d. Burners will re-light when furnace cools down.
2. Check draft safeguard switch.
The purpose of this control is to cause the safe shutdown of the
furnace during certain blocked vent conditions.
a. Verify vent pipe is cool to the touch.
b. Disconnect power to furnace and remove vent connector
from furnace vent elbow.
c. Restore power to furnace and set room thermostat above
room temperature.
d. After normal start-up, allow furnace to operate for 2
minutes, then block vent elbow in furnace 80 percent of
vent area with a piece of flat sheet metal.
e. Furnace should cycle off within 2 minutes. If gas does not
shut off within 2 minutes, determine reason draft safeguard
switch did not function properly and correct condition.
f. Remove blockage from furnace vent elbow.
g. Switch will auto-reset when it cools.
h. Re-install vent connector.
NOTE: Should switch remain open longer than 3 minutes,
furnace control board will lockout the furnace for 3 hours. To reset
furnace control board, turn thermostat below room temperature or
from HEAT to OFF and turn 115v power OFF, then back ON.
3. Check Pressure Switch
This control proves operation of the draft inducer blower.
a. Turn off 115-v power to furnace.
b. Disconnect inducer motor lead wires from wire harness.
c. Turn on 115-v power to furnace.
d. Set thermostat to "call for heat" and wait 1 minute. When
pressure switch is functioning properly, hot surface igniter
should NOT glow and control diagnostic light flashes a
status code 32. If hot surface igniter glows when inducer
motor is disconnected, shut down furnace immediately.
e. Determine reason pressure switch did not function properly
and correct condition.
f. Turn off 115-v power to furnace.
g. Reconnect inducer motor wires, replace outer door, and
turn on 115-v power.
HOOK-AROUND
AMMETER
R Y W G
= 0.5 AMPS FOR THERMOSTAT
ANTICIPATOR SETTING
Table 10–GAS RATE (CU FT/HR)
SECONDS
FOR 1
REVOLUTION
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
A96316
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
h. Blower will run for 90 sec before beginning the call for
heat again.
i. Furnace should ignite normally.
Step 5—Checklist
1. Put away tools and instruments. Clean up debris.
2. Verify that blower OFF-DELAY time is selected as desired.
3. Verify that blower and burner access doors are properly
installed.
4. Cycle test furnace with room thermostat.
5. Check operation of accessories per manufacturer's instruc-
tions.
6. Review User's Guide with owner.
7. Attach literature packet to furnace.
37
SIZE OF TEST DIAL
SECONDS
FOR 1
1
2
5
REVOLUTION
Cu Ft
Cu Ft
Cu Ft
360
720
1800
50
327
655
1636
51
300
600
1500
52
277
555
1385
53
257
514
1286
54
240
480
1200
55
225
450
1125
56
212
424
1059
57
200
400
1000
58
189
379
947
59
180
360
900
60
171
343
857
62
164
327
818
64
157
313
783
66
150
300
750
68
144
288
720
70
138
277
692
72
133
267
667
74
129
257
643
76
124
248
621
78
120
240
600
80
116
232
581
82
113
225
563
84
109
218
545
86
106
212
529
88
103
206
514
90
100
200
500
92
97
195
486
94
95
189
474
96
92
185
462
98
90
180
450
100
88
176
439
102
86
172
429
104
84
167
419
106
82
164
409
108
80
160
400
110
78
157
391
112
76
153
383
116
75
150
375
120
73
147
367
SIZE OF TEST DIAL
1
2
5
Cu Ft
Cu Ft
Cu Ft
72
144
360
71
141
355
69
138
346
68
136
340
67
133
333
65
131
327
64
129
321
63
126
316
62
124
310
61
122
305
60
120
300
58
116
290
56
112
281
54
109
273
53
106
265
51
103
257
50
100
250
48
97
243
47
95
237
46
92
231
45
90
225
44
88
220
43
86
214
42
84
209
41
82
205
40
80
200
39
78
196
38
76
192
38
75
188
37
74
184
36
72
180
35
71
178
35
69
173
34
68
170
33
67
167
33
65
164
32
64
161
31
62
155
30
60
150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

311jav

Table of Contents