Cod. 6316194 - 08/2013 MURELLE EV HE 25-30-35-12 T-20 T-25 T-30 T-35 T INSTALLATION AND SERVICING INSTRUCTIONS ENSURE THAT THESE INSTRUCTIONS ARE LEFT FOR THE USER AFTER COMPLETION OF THE BENCHMARK SECTION PLEASE READ THE IMPORTANT NOTICE WITHIN THIS GUIDE REGARDING YOUR BOILER WARRANTY 199838...
For the first year all of our appliances are protected by our manufacturer’s guarantee which covers both parts and labour. As you would expect from Sime Ltd, it is our aim to provide our valued customers with the best in after sales and service.
Page 4
THE BENCHMARK SCHEME Sime Ltd is a licensed member of the Benchmark Scheme which aims to improve the standards of installation and commissioning of domestic heating and hot water systems in the UK and to encourage regular servicing to optimise safety, efficiency and performance.
Murelle EV HE 20 T: Gas Council number 41-283-20 Murelle EV HE 35: Gas Council number 47-283-19 Murelle EV HE 25 T: Gas Council number 41-283-21 Murelle EV HE 30 T: Gas Council number 41-283-22 Murelle EV HE 35 T: Gas Council number 41-283-23 These appliances comply with the S.E.D.B.U.K.
The products manufactured and sold by to a cylinder the two connections at the based technology to control and manage Sime do not contain any banned left hand side, R3 and M2, need to be all the functions. materials or substances (ie they comply...
Page 7
TECHNICAL FEATURES Models MURELLE EV HE 12 T 20 T 25 T 30 T 35 T Heat output Nominal (80-60°C) 23.9 28.9 34.1 11.7 19.0 23.9 28.9 34.1 Nominal (50-30°C) 26.2 31.6 37.2 12.8 20.9 26.2 31.6 37.2 Reduced G20 (80-60°C) Reduced G20 (50-30°C) Reduced G31 (80-60°C) Reduced G31 (50-30°C)
Page 8
FUNCTIONAL DIAGRAM (fig. 2) MURELLE EV HE 25-30-35 Limit thermostat Primary exchanger Gas valve D.H.W. exchanger Aqua Guard Filter System C.H. sensor (SM) Safety thermostat 100°C Diverter valve Pump with air release vent D.H.W. sensor (SS/SB) D.H.W. flowmeter Hot water inlet filter...
Page 9
MAIN COMPONENTS (fig. 3) MURELLE EV HE 25-30-35 1 Control panel 2 Aqua Guard Filter System 3 Condensate trap 4 Air pressure test point 5 Ignition transformer 6 Safety thermostat 7 C.H. sensor (SM) 8 Ignition electrode 9 Primary exchanger...
INSTALLATION The boiler must be installed in a fixed location and only by specialized and qualified person in compliance with all instructions contained in this manual. The installation of this boiler must be in accordance with the relevant requirements of the current Gas Safety (installation and use), the local building regulations, and and I.E.E.
Page 11
recommended that the system be flushed The sections of the piping making up the condensate pipe to a drain may be in accordance to BS 7593, to eliminate any system must be such as to guarantee a subject local building control foreign bodies that may be detrimental to supply of gas sufficient to cover the...
Page 12
least one radiator should be without a a) The available pump head is given in these methods. thermostatic valve (usually fig. 14. bathroom radiator). b) The appliance is equipped with an d) A sealed system must only be filled by internal by-pass that operates with 2.4.4 Requirements for sealed water...
Page 13
The coaxial suction and discharge from the sum of all the intake and – Sime Ltd recommend only the use of pipes are supplied in a special kit (that discharge pipes, is determined by the...
Page 15
(code 8092227), for the management of a heating circuit. NOTE: SIME declines all responsibility The electronic card will continue to For installation and use of the remote for injury or damage to persons, animals...
Page 16
C.H. return 2.9.5 D.H.W. sensor connection 2.9.6 Use with different in vers. “12-20-25-30-35 T” electronic systems Remote control CR 73 External temperature sensor Zone room thermostat The “12-20-25-30-35 T” version is Some examples are given below of boiler 1-2-3-4 provided with a D.H.W. sensor (SB) linked systems combined with different electro- Zone room thermostat internal to the connector CN5.
Page 17
BASIC SYSTEM: MULTI-ZONE SYSTEM WITH PUMP, ROOM THERMOSTAT AND EXTERNAL SENSOR (Code 8094101) BASIC SYSTEM: MULTI-ZONE SYSTEM WITH VALVE, ROOM THERMOSTAT, REMOTE CONTROL CR 73 (Code 8092226) AND EXTERNAL SENSOR (Code 8094101) PARAMETERS SETTINGS To use the remote control (CR) as remote control panel for the boiler rather than as room reference, set: PAR 7 = 0 BASIC SYSTEM: MULTI-ZONE SYSTEM WITH VALVE, ROOM THERMOSTAT, REMOTE CONTROL CR 73 (Code 8092226) AND...
Page 18
BASIC SYSTEM: MULTI-ZONE SYSTEM WITH PUMP, ROOM THERMOSTAT, REMOTE CONTROL CR 73 (Code 8092226) AND EXTERNAL SENSOR (Code 8094101) PARAMETER SETTING To use the remote control (CR) as room reference for a zone, set: PAR 7 = 1 SYSTEM WITH DOUBLE TEMPERATURE OUTPUT: MULTI-ZONE SYSTEM WITH VALVE, ROOM THERMOSTAT INTERNAL TIME CLOCK AND EXTERNAL SENSOR (Code 8094101) DURING NIGHT TIME THE BOILER USES A LOWER OUTPUT TEMPERATURE IF DIF-...
Page 19
SYSTEM WITH REMOTE CYLINDER PARAMETER SETTING MURELLE T if with D.H.W cylinderto be set: PAR 2 = 3 MURELLE T only for heating to be set: PAR 2 = 4 An alternative to the CR would be to con- M2 R2 nect a room thermostat to the TA 1 con- BOLLITORE CYLINDER...
Page 20
12 SYSTEM WITH MIXER VALVE: SYSTEM WITH TWO DIRECT ZONES AND TWO MIXED ZONES 13 SYSTEM WITH MIXER VALVE: SYSTEM WITH TWO MIXED ZONES INDEPENDENT AND TWO KITS MIXED ZONE (CODE 8092234) 14 SYSTEM SOLAR: SYSTEM WITH KIT SOLAR (Code 8092235) vers.
Page 21
2.10 BOILER ELECTRICAL “MURELLE EV HE 25-30-35” (fig. 11) EXP (24 VRAC) OP (24 VAC) (24 VRAC) (24 VRAC) (5 VDC) Cod. 6301416 SE (5 VDC) TS (24 VDC) TL (24 VDC) SM (5 VDC) (5 VDC) (5 VDC) SS (5 VDC)
Page 22
2.11 BOILER ELECTRICAL “MURELLE EV HE 12-20-25-30-35 T” (fig. 11/a) EXP (24 VRAC) OP (24 VAC) (24 VRAC) (24 VRAC) (5 VDC) Cod. 6301416 (24 VDC) (5 VDC) (24 VDC) (5 VDC) (5 VDC) (5 VDC) D.H.W. tank sensor CONNECTOR SPARE PART CODES: F1-2 Fuse (4 AT) Remote control CR 73 (optional)
ON/OFF KEYS PC CONNECTION ON = Electricity supply to boiler is on To be used only with the SIME programming kit and OFF = Electricity supply to boiler is on but nor ready only by authorised personnel. Do not connect other for functioning.
Page 24
ACCESS TO INSTALLER'S INFORMATION For access to information for the installer, press the key (3 fig. 12). Every time the key is pressed, the display moves to the next item of infor- mation. If the key is not pressed, the system automatically quits the function. List of information. Please note the first key press illuminates the display only: 1.
Page 25
28. Indicator of valve opening control with board Mixed Zone 2 17. Indication of D.H.W. flowmeter load (i.e. 18 l/min and 0.3 l/min) or flow 17. Visualizzazione portata sanitaria flussimetro (es. 18 l/min 26. Visualizzazione comando apertura valvola con schedino (respectively ON and OFF) switch (respectively ON and OFF) e 0,3 l/min) o stato flussostato (rispettivamente ON e OFF)
Page 26
ACCESS TO INSTALLER'S PARAMETERS INSTALLER PARAMETERS FAST CONFIGURATION For access to the installer's parameters, press simultaneously the keys PAR DESCRIPTION RANGE UNIT OF INC/DEC DEFAULT or 5 seconds (3 fig. 12). MEASUREMENT UNIT SETTING For example, the parameter PAR 23 is Combustion configuration -- = ND “--”...
Page 27
PARAMETERS INSTALLER EXTERNAL SENSOR (fig. 13) If there is an external sensor, the heating EXPANSION CARD settings SET can be taken from the climatic curves according to the external PAR DESCRIPTION RANGE UNIT OF INC/DEC DEFAULT temperature and, limited to with the MEASUREMENT UNIT SETTING...
Page 28
(ALL 14). If the D.H.W. sensor (SS) is faulty or open circuit, the boiler will work without modulation to the DHW temperature. TABLE 3 (SM - SS - SF sensors) Temperature (°C) Resistance (Ω) 12.090 con by-pass by-pass on 8.313 senza by-pass by-pass off 5.828...
This operation must be performed by 2) Press button authorised personnel using original seconds Sime components. To convert from natural gas to LPG or vice versa, perform 3) Identify the CO value at max power, the following operations: adjust using the shutter (5 fig. 16): –...
Page 30
15 minutes the boiler will be brought respectively to max and min output. The Code 8109110 chimney sweep function will automatically Model MURELLE EV HE 25 cancel after 15 minutes or if the chimney sweep button is pressed again. Serial n. 9999999999 GC No 47-283-10 4.5.2...
Page 31
boiler will stop and display “ALL 06”. exchanger safety stat open, the burner FUNCTIONING ERRORS Press the reset button on the will turn off. If the stat closes within 1 Where there is a functioning error an control panel (2) to restart the boiler. minute, boiler will...
Page 32
The activation of this probe causes the and the display indicates ALL 22. – FLAME DETECTION ERROR 08 If the flame control detects aflame boiler to stop and error message “ALL During this error the boiler functions when one should not be detected, the 13”...
Page 33
continues to function normally, and and pressurise to 1.5 bar. Ensure that 4.8.2 Burner inspection only the antifreeze function on the the pump has been manually rotated. solar board is active. Open the gas cock, press the “ mode Remove the burner as described in key”...
GAS BOILER SYSTEM COMMISSIONING CHECKLIST This Commissioning Checklist is to be completed in full by the competent person who commissioned the boiler as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference. Failure to install and commission according to the manufacturer’s instructions and complete this Benchmark Commissioning Checklist will invalidate the warranty.
SERVICE RECORD It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed. Service Provider Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer’s instructions. SERVICE 01 SERVICE 02 Date:...
FAULT FINDING If an electrical fault occurs on the appli- approx.: 240 V ac. SHORT CIRCUIT CHECK ance the preliminary electrical system – Test leads from L to E “ ” meter checks must be carried out first. Switches turned FULL ON - meter set on reads approx.
REPLACEMENT OF PARTS – Disconnect wiring from gas valve EXPANSION VESSEL MAIN HEAT EXCHANGER – Disconnect sensing tube – Turn off power supply – Turn off power supply – Remove gas valve – Refit in reverse order ensuring – Remove boiler cover, see 4.4. –...
Page 38
15. Remove the manometer and analyser, close the test points, and check for tightness. – Check for gas soundness. Upstream pressure intake Intermediate pressure intake 6.12 PRINTED CIRCUIT BOARD (PCB) Air signal inlet (VENT) Downstream pressure intake – Isolate from power supply Capacity step –...
Page 40
Pos. Code Description 6138533 Right hand side frame part 6138632 Left hand side frame part 6255431 Expansion vessel lower support 6138894 Frame assembly lower side 6266152 Sealed chamber left hand side panel 6266153 Sealed chamber right hand side panel 6189589 Expansion vessel fixing bracket 6277205 Water trap...
Page 41
Pos. Code Description 6098315 Ignition transformer 6288314 Sealed chamber front panel 5192200 Gasket for sealed chamber 6001210 Peephole 6304700 Control panel 6305160 Guidelight with led 6305120 Kit Rubber button 6247327 Cap for time programmer 6304890 Flap door assembly 64 A 6301416 Main PCB 2211610...
Page 43
Pos. Code Description 6138533 Right hand side frame part 6138632 Left hand side frame part 6255431 Expansion vessel lower support 6138894 Frame assembly lower side 6266152 Sealed chamber left hand side panel 6266153 Sealed chamber right hand side panel 6189589 Expansion vessel fixing bracket 6277205 Water trap...
Page 47
Pos. Code Description 6138533 Right hand side frame part 6138632 Left hand side frame part 6255431 Expansion vessel lower support 6138894 Frame assembly lower side 6266152 Sealed chamber left hand side panel 6266153 Sealed chamber right hand side panel 6189589 Expansion vessel fixing bracket 6277205 Water trap...
Page 48
Pos. Code Description 5183712 Rectang. expansion vessel 8 l. 6226464 O-ring 115 diam. 11,91x2,62 6277723 Pipe connect. exchanger-C.H filter 6295501 C.H. filter 3/4"M x 3/4"M 6277728 Pipe connect. C.H. filter-C.H. flow 6146701 100ˉC safety stat 6231351 Plunged sensor 6243823 Gas valve type 6280590 Three way fitting + cap kit 6017312...
Page 49
Pos. Code Description 6226403 O-ring 2031 107 B 6322350 Hexagonal nozzle diam. 3,80 - MET 107 C 6322352 Hexagonal nozzle diam. 2,90 - LPG 108 B 6322300 Round nozzle diam. 2,80 - MET 108 C 6322302 Round nozzle diam. 2,20 - LPG 6267119 Nozzle locking bracket 6278812...
Page 51
Pos. Code Description 6138533 Right hand side frame part 6138632 Left hand side frame part 6255431 Expansion vessel lower support 6138894 Frame assembly lower side 6266152 Sealed chamber left hand side panel 6266153 Sealed chamber right hand side panel 6189589 Expansion vessel fixing bracket 6277205 Water trap...
Page 52
Pos. Code Description 38 A 5183722 Rectang. expansion vessel 10 l. 6226464 O-ring 115 diam. 11,91x2,62 43 A 6277721 Pipe connect. exchanger-C.H filter 6295501 C.H. filter 3/4"M x 3/4"M 6277728 Pipe connect. C.H. filter-C.H. flow 6146701 100ˉC safety stat 6231351 Plunged sensor 6243823 Gas valve type...
Page 53
Pos. Code Description O-Ring diam. 52,07 x 2,62 6226470 Mixer 105 B 6274371 O-ring 2031 6226403 Hexagonal nozzle diam. 4,00 - MET 107 D 6322353 107 E 6322354 Hexagonal nozzle diam. 3,00 - LPG 108 B 6322300 Round nozzle diam. 2,80 - LPG Round nozzle diam.
APPENDIX 1 INDUSTRY GUIDANCE FOR INSTALLERS ON CONDENSATE DRAINAGE PIPE INSTALLATION This guidance is endorsed by HHIC members. 1. BACKGROUND During recent winters the UK has experienced prolonged spells of extremely cold weather - down to minus 20 C and below in many areas. This resulted in a significant increase in the number of calls to boiler manufacturers and heating engineers from householders with condensing (high efficiency) boilers where the condensate drainage pipe had frozen and become blocked with ice, causing the boiler to shut down.
Page 55
2.1 INTERNAL TERMINATION: Wherever possible, the condensate drainage pipe should be terminated at a suitable internal foul water discharge point such as (a) an internal soil and vent stack or (b) an internal kitchen or bathroom waste pipe, washing machine waste pipe etc. A suitable permanent connection to the foul waste pipe should be used.
Page 56
The use of fittings, elbows etc should be kept to a minimum and any internal “burrs” on cut pipework should be removed so that the internal pipe section is as smooth as possible. The customer/householder should be advised that even with the above measures this type of installation could freeze, and that if this were to occur then boiler shutdown could result, requiring remedial action - possibly involving a chargeable engineer call-out.
Page 57
NOTES The Benchmark Commissioning Checklist (located at the back of the boiler installation manual) should be completed as required to record details of the condensate drainage pipe installation. Where an external condensate drainage pipe is installed, the customer should be made aware of the risks and consequences of its freezing and offered the option to fit trace heating (or other measures approved by the boiler manufacturer or service organisation).
Page 58
Figure 1 – Connection of condensate drainage pipe to internal soil and vent stack Boiler Visible air break 75 mm trap Visible air break and trap not required if there is a trap with a minimum condensate seal of 75 mm incorporated into the boiler Soil and vent stack Invert 450 mm minimum up to three storeys...
Page 59
Figure 2(a) – Connection of a condensate drainage pipe downstream of a sink, basin, bath or shower waste trap Boiler Visible air break 75 mm trap Visible air break and trap not required if there is a trap with a minimum condensate seal of 75 mm incorporated into the boiler.
Page 60
Figure 2(b) – Connection of a condensate drainage pipe upstream of a sink, basin, bath or shower waste trap Boiler Visible air break at plug-hole 75 mm sink, basin, bath or shower waste trap Sink, basin, bath or shower with integral overflow Open end of condensate drainage pipe direct into gully 25 mm min below grating but above water level;...
Page 61
Figure 3 – Connection of a condensate pump - typical method (NB manufacturer’s detailed instructions should be followed). IND GUIDE INST 10-11 HHIC REF T11/0027BRev8...
Page 62
Figure 4 – Connection of condensate drainage pipe to external soil and vent stack Boiler 450 mm minimum up to three storeys Visible air break Minimum internal diameter 19 mm 75 mm trap Pipe size transition point Visible air break and trap not required if Minimum internal diameter 30 mm there is a trap with a minimum condensate Water/weather proof insulation...
Page 63
Figure 5 – External termination to rainwater downpipe (NB only combined foul/rainwater drain) Condensate discharge pipe from boiler Air gap Pipe size transition point 68 mm PVCu strap-on fitting Water/weather proof insulation Minimum internal diameter 19 mm 43 mm 90° male/female bend Minimum internal diameter 30 mm External rain water pipe into foul water End cut at 45 °...
Page 64
Figure 6 – External drain, gully or rainwater hopper Boiler Visible air break 38 mm minimum trap Visible air break and trap not required if there is a trap with a minimum condensate seal of 38 mm incorporated into the boiler External length of pipe 3 m maximum Open end of condensate drainage pipe direct into gully 25 mm min below grating but above water level;...
Page 65
Figure 7 – Example of a purpose-made soakaway Condensate discharge pipe from boiler Ground (this section of the condensate drainage pipe may be run either above or below ground level); End cut at 45 ° Diameter 100 mm minimum plastic tube Bottom of tube sealed Limestone chippings Two rows of three 12 mm holes at 25 mm centres, 50 mm from bottom of tube and...
Turn off appliance and call SIME LTD Technical HelplIne for advice. NOTE - if no flue gas sampling point is present and the correct pro- cedure is not specified in the manual, contact SIME LTD Technical the appliance must not be commissio- Helpline for advice.