Carrier ETN Installation Instructions Manual page 9

Table of Contents

Advertisement

NON-PROGRAMMABLE THERMOSTAT
MODELS « 50PZ / 38PZ + 40PZ 031-075 »
THERMOSTAT TERMINALS
Y 1
G
Y 2
S
S
W 2
E
Y 1
G
Y 2
1 7
UNIT ELECTRICAL BOX TERMINALS
(Heat pump Models)
MICROS BLOCK S1
1-3-4-5-6
Micro No.
2
Micro No.
O F F
Position
O N
Position
IMPORTANT:
E W 1 O
C
R
To check if the Unit has a
jumper befween «R & 16»
or «R & 17».
If yes, this jumper must be
removed before doing new
thermostat connections.
1 6
W 1
O
C
R
MICROS BLOCK S2
2
1-3-4-5-6
O F F
O N
REF.- ETN.12
10-06-05
- 28 -
The micro-switches are factory configured by default in the following position:
BLOCK S1
Micro No.
Position
2
O N
1, 3, 4, 5, 6
OFF
5.3 Atmospheric or remote return sensor connection (optional)
NTC Sensor: Temperature~Resistance Features
Temp ºC
7.2
10.0
12.8
15.6
Resist. k
115.8
100.9
88.1
77.1
Factory configuration includes an internal sensor.
·
Disconnect the 24 vac power supply to the thermostat.
·
Set micro-switches 1, 2, 3 on block S2 as required.
·
Connect the temperature sensor to terminals S and S.
·
Reconnect the 24 vac. power supply.
·
Use shielded-type wiring to connect the sensor.
BLOCK S2
Micro No.
Position
1, 3, 6
O N
2, 4, 5
OFF
18.3
21.1
23.9
26.7
29.4
32.2
67.7
59.6
52.5
46.4
41.2
36.6
- 9 -