Carrier EDGE Pro Installation Instructions Manual

Carrier EDGE Pro Installation Instructions Manual

Programmable commercial thermostat

Advertisement

Part Numbers 33CS2PPRH-03 and 33CS2PP2S-03
IMPORTANT: Read entire instruction before installing
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
PACKAGE CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION CONSIDERATIONS . . . . . . . . . . . . . .1,2
Control Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Outdoor Temperature Sensor . . . . . . . . . . . . . . . . . . . . 2
Remote Indoor Temperature Sensor. . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Thermostat Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Wiring Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Two-Piece Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Single-Piece Installation . . . . . . . . . . . . . . . . . . . . . . . . . 5
Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
(33CS2PPRH-03 Model Only). . . . . . . . . . . . . . . . . . . . 6
CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-11
To Enter and Exit Configuration Mode. . . . . . . . . . . . 6
Configuration Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Configuration Options . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
SYSTEM START-UP AND CHECKOUT . . . . . . . . .11,12
Installer Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Default Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
and Holiday Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
(33CS2PPRH-03 Model Only). . . . . . . . . . . . . . . . . . . 11
Holiday. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12,13
Unoccupied Overrride. . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Equipment On Indicators. . . . . . . . . . . . . . . . . . . . . . . . 13
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
®
Auto Changeover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Emergency Heat Mode . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Dry Contact/Economizer Output . . . . . . . . . . . . . . . . 13
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . .13,14
Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . 14-25

SAFETY CONSIDERATIONS

Read and follow manufacturer instructions carefully. Fol-
low all local electrical codes during installation. All wiring
must conform to local and national electrical codes. Improper
wiring or installation may damage sensor.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53330026-01

Installation Instructions

Printed in U.S.A.
Commercial Thermostat
Recognize safety information. This is the safety alert sym-
bol
. When the safety alert symbol is present on equipment
or in the instruction manual, be alert to the potential for person-
al injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety alert symbol.
DANGER identifies the most serious hazards which will result
in severe personal injury or death. WARNING signifies a haz-
ard which could result in personal injury or death. CAUTION
is used to identify unsafe practices which would result in minor
personal injury or property damage.
Carrier's 7-day, 5/2-day, or 1-day programmable commer-
cial thermostat control is a wall-mounted, low-voltage control
which provides temperature control in either a single unit or a
two-piece unit. The 33CS2PPRH-03 thermostat will provide
both temperature and humidity control. In the two-piece con-
figuration, the relays are located near the equipment and a two-
wire connection is used between the display module (DM, the
user interface) and the equipment control module (ECM). Sin-
gle-piece installation requires more wiring and results in a
higher profile. The thermostat needs no batteries to store user-
configured settings in memory. If power is lost, the internal
memory saves settings for unlimited time and the clock contin-
ues to run for at least 24 hours.
In the programmable configuration, different heating and
cooling set points and times are programmable for 4 periods
per day or 2 periods per day. Programming can be done for
7 days per week, 5 and 2 days per week, or 1 day. The pro-
grammable control can also be user-configured as a non-
programmable control.

PACKAGE CONTENTS

1 - Display module
1 - Stand-off for equipment control module
2 - Screws and anchors
1 - Pigtail
1 - Equipment control module with cover

INSTALLATION CONSIDERATIONS

There are two types of thermostats available. The
33CS2PP2S-03 thermostat provides temperature control and
the 33CS2PPRH-03 thermostat provides both temperature and
humidity control. Both models can be configured for air condi-
tioner or heat pump installations and may be configured as
non-programmable, if desired.

Control Configuration -

stalled in one of two configurations. The thermostat may be in-
stalled as a single piece or it may be split into two pieces and
mounted in separate locations.
Form 33CS-74SI
Pg 1
®
EDGE
Programmable

GENERAL

The thermostat can be in-
6-13
Replaces: 33CS-66SI
Pro

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EDGE Pro and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Carrier EDGE Pro

  • Page 1: Table Of Contents

    Thermostat Location ......2 Carrier’s 7-day, 5/2-day, or 1-day programmable commer- Wiring Requirements......2 cial thermostat control is a wall-mounted, low-voltage control Two-Piece Installation .
  • Page 2: The Thermostat

    Wire length should not exceed 1,000 ft. NOTE: Carrier sensor part no. 33ZCT55SPT would be used for • For wiring the control module to the equipment, the dis- remote space sensing averaging. Sensors must be used as a sin-...
  • Page 3 6. During thermostat installation provide sufficient excess wiring behind the mounting plate. Coil the wiring creating a service loop and place in mounting box or behind the wall to remove strain against the terminal strip. See Fig. 4. a33-9162 Fig. 1 — Locking Tab Location Fig.
  • Page 4 14. Find a suitable indoor mounting location for equipment control module. The module should be mounted on or near the HVAC equipment. See Fig. 8. a33-9166 Fig. 6 — Pigtail Connection Fig. 8 — Equipment Control Module Mounting 10. Connect red wire of the pigtail to V+ RED terminal. Con- 15.
  • Page 5: Single-Piece Installation

    RELAYS OAT/RRS SRTN RETURN CONTACT SEPARATE RC/RH BY CONNECT O/W2/B TO USER BREAKING BLACK INTERFACE JW6 ON CONTROL MODULE BOARD. a33-9170 LEGEND — Outdoor Air Temperature Sensor — Remote Room Temperature Sensor Fig. 10 — Control Module Connector Block Terminals only, the equipment control module does not need to be leveled for proper operation) and mark wall through two mounting holes.
  • Page 6: Power

    13. Attach display module body to equipment control module CONFIGURATION by first setting the module on at top of equipment control Press To Enter and Exit Configuration Mode — module and then snapping the bottom corners of display and hold OCCUPIED button for approximately 10 seconds. module into place.
  • Page 7: Configuration Options

    (r), or the average of local and remote that energizes its reversing valve (O/W2/B) in heating. sensors (Lr). The Carrier sensor 33ZCT55SPT would be used NOTE: The WSHP will always energize the reversing valve in for remote space sensing and averaging. Settings are L, r, or Lr.
  • Page 8 set to OF, then Auto mode is not available. Allowable selections NOTE: This configuration is only available if Option 34 is set to are On and OF (off). The default is On. od or if a valid sensor is connected. OPTION 16 —...
  • Page 9 3 — Without Unlock Code Configuration settings are OF (off), 20, 25, 30, 35, 40, 45, 50 F (–6.7, –3.9, –1.1, 1.7, 4.4, 7.2, 10 C) and On. The entire keypad will be locked. When the user presses a but- ton, the backlight turns on to maximum brightness for 10 sec- When set to OF (off), heating always starts in low stage (Y1) onds but none of the thermostat operating parameters will be...
  • Page 10 When set to OF (off), the Daylight Savings Time Function NOTE: In a non-heat pump application, if emergency heat is disabled. is off, the second stage of heat will show “heat on” and “2” in the bottom right of the thermostat display. The first time the UP or DOWN button is pressed, the value of this selection changes from OF (off) to 1.
  • Page 11: System Start-Up And Checkout

    button is kept pressed until the count reaches zero, the reset will Setting the Clock, Calendar, Daily Schedule, be performed. To set the clock, press the SET and Holiday Settings — button once. The clock will be displayed at the bottom center of When the value reaches zero, the heat set point will display the screen.
  • Page 12: Holiday

    humidity is 1% above set point and are terminated when humidi- ty drops to 4% below set point. This prevents unnecessary tog- 3 2 1 gling of dehumidification actions when humidity is near the set point. A holiday selection is available specifically for Holiday —...
  • Page 13: Timers

    When holiday is active and the OCCUPIED button is When the outdoor-air temperature is below the heat pump pressed, the temporary hold timer is set for two hours, the heat lockout temperature, the heat pump will not be energized. The and cool set points change to the occupied settings, the humidity gas heat source will be used to satisfy the heating demand.
  • Page 14: Error Codes

    Y/Y2 O/W2/B O/W2/B WIRING DIAGRAMS Y/Y2, Y/Y2, W/W1 (WSHP) O/W2/B Y/Y2 O/W2/B W/W1 System wiring diagrams are provided for typical Carrier equipment. See Fig. 15-36. LEGEND — Reversing Valve COMMERCIAL THERMOSTAT UNIT CTB THERMOSTAT a33-9292 O/W2/B SRTN Humidi-MiZer® FIOP †...
  • Page 15 COMMERCIAL THERMOSTAT TERMINAL BOARD W2† O/W2/B a33-9287 SRTN *Connection not required. †W2 connection not required on units without electric heating. Fig. 16 — Thermostat Wiring — 50HCQ,TCQ Rooftop Units COMMERCIAL THERMOSTAT CONNECTION BOARD / TB2† O/W2/B SRTN Humidi-MiZer® FIOP LTLO a33-9174 LEGEND *Connection not required.
  • Page 16 COMMERCIAL THERMOSTAT 48/50HJ,62AQ COBRA UNIT BASE UNIT CONNECTION BOARD a33-9175 W/W1 Y/Y2 O/W2/B ENERGY$RECYCLER SRTN CONNECTION BOARD *Connection not required. Fig. 18 — Thermostat Wiring — 48/50HJ,62AQ060-300 COBRA™ Energy Recovery Units COMMERCIAL THERMOSTAT TB1 / TB2† a33-9176 O/W2/B SRTN Humidi-MiZer® FIOP *Connection not required.
  • Page 17 COMMERCIAL THERMOSTAT O/W2/B a33-9281 IPD/X* SRTN *Connection not required. Fig. 20 — Thermostat Wiring — 50HJQ014,016 Heat Pump Units COMMERCIAL THERMOSTAT a33-9179 O/W2/B SRTN Fig. 21 — Thermostat Wiring — 50EJQ,EWQ024,028 Heat Pump Units...
  • Page 18 COMMERCIAL THERMOSTAT CONNECTION BOARD (TB) O/W2/B a33-9298 LLSV-1 X*/8 SRTN LLSV-2 38ARD007-02 38ARD014-024 LEGEND — Indoor Fan Contactor *Connection not required. LLSV — Liquid Line Solenoid Valve Fig. 22 — Thermostat Wiring — 38ARD Commercial Split System Units COMMERCIAL THERMOSTAT INDOOR UNIT O/W2/B FAN COIL...
  • Page 19 INDOOR OUTDOOR CONNECTION CONNECTION COMMERCIAL THERMOSTAT BOARD (TB) BOARD (TB) a33-9286 O/W2/B SRTN ONLY REQUIRED FOR 38AUQ HEAT PUMP Fig. 24 — Thermostat Wiring — 38AU Commercial Split System Units with 40RUA Air Handler Units TERMINAL BLOCK JUMPER FOR ELECTRIC HEAT HEAT PUMP ACCESSORY WIRING...
  • Page 20 COMMERCIAL THERMOSTAT COMPLETE C a33-9285 O/W2/B FIRST COMPRESSOR SRTN Fig. 26 — Thermostat Wiring — 50HQL, KQE, KQL, P1, PC, PEC, PS, PSW, PT, RHC, RHE, RHR, RHS, RTG, RVC, RVE, RVR, RVS, RWS,VQL Water Source Heat Pump Units with Complete C Controls a33-9284 COMMERCIAL THERMOSTAT DUCT HEATER...
  • Page 21 COMMERCIAL THERMOSTAT DELUXE D a33-9183 O/W2 O/W2/B SRTN Fig. 28 — Thermostat Wiring — 50HQL, KQE, KQL, P1, PC, PEC, PS, PSW, PT, RHC, RHE, RHR, RHS, RTG, RVC, RVE, RVR, RVS, RWS, VQL Water Source Heat Pump Units with Deluxe D Controls COMMERCIAL THERMOSTAT DELUXE D Y/Y2...
  • Page 22 COMMERCIAL THERMOSTAT a33-9288 O/W2/B SRTN Fig. 30 — Thermostat Wiring — 50VS Water Source Heat Pump Units COMMERCIAL THERMOSTAT INDOOR FAN BOARD (IFB) a33-9291 ORANGE GREEN WHITE O/W2/B BLACK Y2/DH YELLOW Y1/Y BROWN SRTN COMMON *Model 33CS2PP2S-03 thermostats only. ® Fig.
  • Page 23 COMMERCIAL THERMOSTAT a33-9185 O/W2/B OAT SENSOR SRTN REMOTE ROOM SENSOR Fig. 32 — Thermostat Wiring — Outdoor Air Temperature and Remote Room Temperature Sensors COMMERCIAL THERMOSTAT a33-9186 O/W2/B SRTN HUMIDIFIER DEHUMIDIFIER/ NOTES: 3. For humidifer control, 24-V is provided from the HUM terminal to 1.
  • Page 24 COMMERCIAL THERMOSTAT a33-9187 O/W2/B SRTN HUMIDIFIER NOTES: 3. For humidifer control, 24-V is provided from the HUM terminal to 1. D1 and D2 can be used independently for equipment requiring a operate the equipment. dry contact. 4. For fan control, 24-V is applied from Rh to the fan (G) through 2.
  • Page 25 COMMERCIAL THERMOSTAT STRN SENSOR 1 SENSOR 2 SENSOR 3 SENSOR 4 SENSOR 5 SENSOR 6 a33-9280 SENSOR 7 SENSOR 8 SENSOR 9 Fig. 36 — Thermostat Wiring — Space Temperature Sensor Averaging Wiring (9 Sensor Application)
  • Page 26 © Carrier Corporation 2013 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53330026-01 Printed in U.S.A. Form 33CS-74SI Pg 26 6-13 Replaces: 33CS-66SI...
  • Page 28: Thermostat Configuration Record

    Maximum Temporary Hold For Hours Option 39 _____ Temperature Display © Carrier Corporation 2013 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53330026-01 Printed in U.S.A.

This manual is also suitable for:

Edge pro 33cs2pprh-03Edge pro 33cs2pp2s-03