Table 2 Double pipe sub-gravity feed system
Maximum allowable pipe run (metres)
Head
8mm inside dia. pipe
10mm inside dia. pipe
(m)
(10mm OD copper)
(12mm OD copper)
0
50
100
-0.5
44
100
-1.0
38
95
-1.5
32
80
-2.0
26
66
-2.5
20
51
-3.0
14
37
-3.5
8
22
Table 3 Single pipe suction lift with de-aerator
Maximum allowable run from tank to de-aerator (metres)
Fuel flow rate
2.5(kg/h)
Head (m)
6mm inside dia. pipe (8mm OD copper)
0
100
0.5
95
1.0
80
1.5
70
2.0
60
2.5
45
3.0
35
3.5
25
Oil filters
Oil filters must always be incorporated in the oil supply
line, one on the outlet from the oil tank to filter deposits
from within the tank or fuel and one near the appliance to
filter deposits from within the fuel line itself. They are
supplied and fitted by the installing engineer and are not
part of the boiler's components. They should be able to be
serviced without the need for draining down the fuel supply
line. There must be sufficient clearance below the filter to
enable servicing operations to be carried out easily. Filters
must comply to OFTEC standard OFS E104.
36
Fire valves
A fire valve is an essential part of the oil supply system. It is
supplied and fitted by the installing engineer and is not part
of the boiler's components. Its purpose is to cut off the
flow of oil outside the building in the event of fire within
the boiler area. The valve should be located at the point of
entry into the building of the fuel line. It must be activated
by a remote sensor located over the burner. A clip is
provided within the appliance for the sensor. Fire valves
must comply with OFTEC standard OFS E101.
Fig. 10 Single pipe system
Maximum oil level
Wall
Paper element
oil filter
Fire
Oil tank
Filter
Fire valve to
detection
element
BS 5410
Full base
(for plastic tanks)
Isolating
valve
Isolating
Isolating
valve
valve
Burner
Two pipe systems
Fig. 11 Two pipe system
Non return
Fire detection
valve
Wall
element
Oil tank
Filter
Non return
valve
Isolating
Isolating
Burner
valve
valve
150mm
Full base
Isolating
Fire valve to
(for plastic tanks)
valve
BS 5410
Fig. 12 Single pipe lift system with de-aerator
Fire detection
Wall
element
De-aerator
Oil tank
Filter
Fire valve to
BS 5410
Burner
Full base
Isolating
Isolating
(for plastic tanks)
valve
valve
Warranty
Worcester oil-fired appliances are offered with a 2 year*
guarantee on parts and labour from the date of installation
if the appliance is commissioned upon installation and the
regular service requirements are met. The primary heat
exchanger comes with a 5 year* warranty. Ongoing service
and maintenance contracts can be arranged through the
Worcester Customer Service Department.
*Subject to conditions.
Greenstar Heatslave series accessories
(kitchen models)
Horizontal flue kit
Vertical flue kit
(125mm dia.)
(125mm dia.)
Worcester Part No.
Worcester Part No.
7 716 190 031
7 716 190 032
Flue extension
45º bend
(125mm dia.)
(125mm dia.)
Worcester Part No.
Worcester Part No.
7 716 190 033
7 716 190 035
Digital plug-in 7 day twin
Flat roof flashing kit
channel programmer
(100mm & 125mm dia.)
Worcester Part No.
Worcester Part No.
7 716 192 033
7 716 191 090
Stainless steel flue
1,000mm extension kit
terminal guard
Worcester Part No.
100mm dia.
7 716 190 066
130mm dia.
Worcester Part No.
7 716 190 070
7 716 190 050
Telescopic flue kit
Telescopic flue kit
short (125mm dia)
standard (125mm dia)
Worcester Part No.
Worcester Part No.
7 716 190 062
7 716 190 064
90º bend
Conventional
(125mm dia.)
flue adaptor
Worcester Part No.
Worcester Part No.
7 716 190 034
7 716 190 036
Pitched roof flashing kit
Oilfit flexible flue kit
(100mm & 125mm dia.)
Worcester Part No.
Worcester Part No.
7 716 191 091
100mm dia.
7 716 190 076 (8m)
500mm extension kit
7 716 190 077 (12m)
7 716 190 078 (15m)
130mm dia.
7 716 190 079 (8m)
7 716 190 080 (12m)
7 716 190 081 (15m)
Worcester Part No.
100mm dia.
7 716 190 067
130mm dia.
7 716 190 071
37

Advertisement

Table of Contents
loading

This manual is also suitable for:

Greenstar heatslave 18/25Greenstar heatslave 25/32

Table of Contents