Installation: 42Vmc009N - 012N - 014N - 018N - 024N - Carrier 42VMC---N Installation Manual

Table of Contents

Advertisement

42VMC---N
Installation: 42VMC 009N - 012N - 014N - 018N - 024N
42VMC---N
009
012
A
mm
850
850
B
mm
786
786
C
mm
237
237
D
mm
237
237
Drilling the hole in the wall for the
connection of the pipes
The pipes can exit the unit to three different directions (see
illustration). For exit to the rear, the wall hole must be made in the
position shown in the illustration.
Indoors
Outdoors
Drill a 70 or 80 mm diameter hole.
The hole must have a 5-10 mm downward slope towards the
outside. Insert the plastic conduit provided.
Pass the electrical connecting wires through the conduit (see
electrical connections).
C
D
A
B
014
018
1000
1000
940
940
250
250
285
285
Ø 80 mm
50 mm
Condensate drain pipe
For vertical installation
Connect the PVC pipe to the connection on the drain pan.
A Refrigerant connections
B Condensate drain pipe
IMPORTANT:
The outdoor unit is designed to operate without the use of
condensate water to cool the condenser coil.
It is necessary to discharge the condensate directly into
the sewer system, downpipes or to disperse it outside.
For horizontal installation
To allow the condensate drain pipe to correctly come out of the
unit, proceed as follows:
024
1000
940
250
285
• Remove from suction grille, the part of grille fixed tonguing,
pressing it until tabs is unhooked.
Mount condensate drain pipe cover
necessary. In the event of condensate discharge pump is used
(accessory), the condensate drain pipe can exit together with
the refrigerant pipes.
E N G L I S H
A
B
supplied, fitting it as
GB - 7